Plan Review Notes For Permit 17020407 |
Permit Number |
17020407 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-16 14:56:09 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. THE DESCRIPTION STATES THIS IS FOR THE GENERATOR | | ROOM. THE PERMIT NUMBER IS FOR THE HIGH RISE. IT IS NOT | | CLEAR WHETHER THIS SHOULD BE ASSOCIATED WITH THE | | GENERATOR BUILDING PERMIT, OR THE HIGH RISE. PROVIDE A | | PLAN SHOWING LOCATION AND SIZE(S) OF PROPOSED LOUVERS, | | FBC 107. IF THIS IS FOR THE GENERATOR BUILDING, REVISE | | THE SUBMITTAL SHEET TO REFER TO THE CORRECT PERMIT (AND | | HAVE CHANGED WHEN RESUBMITTING AT THE FRONT COUNTER). | | | | 2. PROVIDE THE PRODUCT APPROVAL FOR THIS EXHAUST FAN, | | FBC 1609. PRIOR TO SUBMITTAL, PLEASE ENSURE THAT THE | | DRAWING SHEETS ARE PRINTED IN LANDSCAPE ORIENTATION. | | PORTRAIT ORIENTATION RESULTS IN DRAWINGS WHICH ARE | | INTENDED TO BE 11X17 TO BE PRINTED 1/4 ORIGINAL SIZE. |
|