Plan Review Notes For Permit 17020400 |
Permit Number |
17020400 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-03 12:56:12 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE 2010 | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. THE PRODUCT APPROVALS ARE NOT LEGIBLE. FOR THE | | DRAWING PAGES ARE REDUCED AND OF POOR QUALITY. PLEASE | | RE-PRINT. THE PRODUCTS WILL BE REVIEWED FOR COMPLIANCE | | WITH THE DESIGN PRESSURES SPECIFIED ON SHEET S8.5. | | | | 2. DOOR TAGS ON THE FLOOR PLAN ARE NOT LEGIBLE. IT | | APPEARS THAT MANY DOORS MAY BE PARTIALLY IN ZONE 5. ON | | THE PRODUCT APPROVAL, INDICATE WHICH OF THE DOOR | | OPTIONS IS PROPOSED. IF A DOOR IS LOCATED IN VERY CLOSE | | PROXIMITY TO THE CORNER, SHOW DISTANCE ON THE PLAN. | | DESIGN PRESSURES SPECIFIED BY ENGINEER ARE 52.5 / -52.5 | | ZONE 4, 52.5/-95.7 ZONE 5. THE LOCATION PLAN SHOULD | | CLARIFY WHICH DOORS, IF ANY, ARE IN ZONE 5. | | | | | | | | |
|