2017-02-28 07:13:421) SUBMIT A SITE PLAN SHOWING THE LOCATION OF BOTH
 GENERATORS IN RELATION TO OPERABLE WINDOWS, DOORS AND
 ANY OTHER OPENINGS INTO THE STRUCTURE. WPB AMEND. TTO
 FBC SEC. 107.2.1.
 2) SHOW THE DISTANCES FROM THE GENERATOR EXHAUST TO ALL
 OPERABLE WINDOWS AND DOORS AND ANY OTHER OPENINGS INTO
 THE STRUCTURE. COMPLY WITH NFPA 58 & NFPA 37. WPB
 AMEND. TTO FBC SEC. 107.2.1.
 3) SHOW THE LOCATION OF THE EXISTING LP TANK ON THE
 SITE PLAN. WPB AMEND. TTO FBC SEC. 107.2.1.
 4) THE PLANS REFERENCE TWO PE SIZING TABLES IN THE FUEL
 GAS CODE BUT YOU HAVE ALSO SUBMITTED A SIZING TABLE
 FROM THE MANUFACTURER. CLARIFY.
 5) THE PLANS SHOW THE UNDERGROUND LP PIPING AS EXISTING
 BUT YOU HAVE SUBMITTED MANUFACTURER'S SPECIFICATIONS
 FOR PE PIPING. CLEARLY INDICATE ON THE PLANS IF ANY NEW
 PE PIPING IS BEING INSTALLED AND LIST THE TOTAL
 DEVELOPED LENGTH AND PSI OF THE SYTEM ON THE NEW PE
 PIPE. WPB AMEND. TTO FBC SEC. 107.2.1.THE PLANS NOTE
 THIS AS A DISCONNECT/RECONNECT.CLARIFY.
 6) THE PLANS SHOW ONE OF THE GENERATORS WITH A BTU LOAD
 OF 340,000. THERE ARE TWO GENERATORS BEING INSTALLED SO
 THE BTU LOAD SHOULD BE 680,000 BUT THE TOTAL LOAD SHOWN
 ON THE PLAN IS 340,000. CLARIFY. THE PIPING SHALL BE
 SIZED FOR THE TOTAL BTU LOAD ON THE SYSTEM.AS SHOWN,
 THE SYSTM IS UNDERSIZED.
 7) SHOW THE DEVELOPED LENGTH OF THE SCH. 40 METALLIC
 PIPE FROM THE STEP- DOWN REGULATOR TO EACH GENERATOR.
 8) THE GAS SIZING TABLES THAT ARE REFERENCED ON THE
 PLAN FROM THE 2014 FBC-FUEL GAS CODE ARE FOR NATURAL
 GAS AND THIS IS AN LP GAS SYSTEM. REFERENCE THE CORRECT
 APPLICABLE SIZING TABLES ON THE PLANS. INCLUDE THE
 REFERENCE TO THE CORRECT TABLE FOR THE METALLIC PIPE.
 WPB AMEND. TTO FBC SEC. 107.2.1.
 9) CLARIFY THE PIPE RUN OF 30 FEET SHOWN ON THE
 PLANS.IS THIS FOR THE EXISTING UNDERGROUND? INDICATE
 THE PSI OF THE EXISTING SYSTEM FROM THE LP TANK TO THE
 REGULATOR. WPB AMEND. TTO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  