Date |
Text |
2017-06-28 14:42:40 | 2ND REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: 2ND REQUEST NOT COMPLIED |
| |
| 1. GRAB BARS SHALL BE INSTALLED ABOVE THE FINISH FLOOR |
| MEASURED TO THE TOP OF THE GRIPPING SURFACE,PER FBC ACC |
| 609.4 |
| |
| 2. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. PER FBC ACC 604.7 |
| |
| 3. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION, PER FBC |
| ACC 604.2 |
| |
| 4. PROVIDE DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH |
| FBC ACC 608 PER FBC ACC 213.3.6 |
| A) 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. |
| STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30 |
| INCHES (760 MM) WIDE MINIMUM BY 60 INCHES (1525 MM) |
| DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER |
| POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES |
| (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER |
| COMPARTMENT. |
| B) 608.2.2.1 CLEARANCE. |
| A 30 INCH (760 MM) WIDE MINIMUM BY 60 INCH (1525 MM) |
| LONG MINIMUM CLEARANCE SHALL BE PROVIDED ADJACENT TO |
| THE OPEN FACE OF THE SHOWER COMPARTMENT. |
| C) 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. |
| WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE |
| SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE |
| BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB |
| BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT |
| IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER |
| COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE |
| WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES (150 MM) |
| MAXIMUM FROM ADJACENT WALLS. |
| D) 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. |
| IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE |
| CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 |
| INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT |
| IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY |
| UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO |
| THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM) |
| MAXIMUM FROM THE SEAT WALL. |
| |
| |
| 5. PROVIDE SANITARY AND WATER RISER DIAGRAM . PER WPB |
| AMEND TO FBC 107.3.5.1.3(13) |
| |
| 5. PROVIDE MANUFACTURE SPECS FOR SUMP PUMP AND OIL |
| INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| |
| DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| |
| WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| |