Plan Review Notes
Plan Review Notes For Permit 17020366
Permit Number 17020366
Review Stop M
Sequence Number 2
Notes
Date Text
2017-06-30 08:35:592ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17020366
 6/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE RESUBMITTED PLANS DO NOT APPREAR TO BE CORRECTED
 PER THE 1ST REVIEW COMMENTS. MANY OF THE DEFICIENCIES
 STILL EXIST, AND NO NARRATIVE FROM THE ENGINEER WAS
 SUBMITTED IN RESPONSE WHICH TYPICALLY HELPS TO CLARIFY
 AND EXPEDITE THE REVIEW PROCESS. I AM REPRINTING THE
 1ST REVIEW COMMENTS BELOW. PLEASE NOTE THAT THE
 BUILDING PLAN REVIEWER'S SECOND REVIEW COMMENTS ARE
 STATING THAT THE RESUBMITTED PLANS ARE INDICATING A NEW
 SECOND FLOOR WALL MUST BE CONSTRUCTED TO SEPARATE THE
 ATRIUM FROM THE SECOND FLOOR LEVEL. THIS REQUIRED
 REDESIGN WILL OBVIOUSLY IMPACT THE CURRENT HVAC DESIGN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 1ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020366
 2/14/17
  
 1) SHEET M1.01: THE SUMMARY "WHOLE SYSTEM HEAT LOADS"
 ARE INCOMPLETE- SEE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION AND PROVIDE CALCULATIONS IN ACCORDANCE
 WITH ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N. SUMMARY
 CALCULATIONS PER THE EXCEPTION MUST INCLUDE ITEMS 1-13,
 BE PERFORMED FOR EACH ZONE, AND BE SUBMITTED ON A
 SIGNED AND SEALED SUMMARY SHEET.
  
 2) M1.01: PLEASE BREAKDOWN THE VENTILATION CALCULATIONS
 FOR THE BEAUTY/NAIL SALON TO PROVIDE 50 CFM PER NAIL
 TABLE AND 0.60 CFMS PER SF FOR THE SALON. THE CURRENT
 PLAN APPEARS TO BE NON-COMPLIANT WITH ONLY THE EF-1
 FUNCTIONING IN THE AREA.
  
 3) M1.01 & M1.02: THE PLAN INDICATES AIR IN THE BEAUTY
 SALON IS BEING RECIRCULATED INTO OTHER ROOMS AND SPACES
 WHICH IS PROHIBITED PER TABLE 403.3 FOOTNOTE B- PLEASE
 CORRECT.
  
 4) M1.01: EXHAUST VENTILATION IS REQUIRED FOR THE
 SHOWER- SEE TABLE 403.3 AND PROVIDE A SYSTEM.
  
 5) M1.01: INDICATE HOW OUTSIDE AIR IS BEING SUPPLIED TO
 AHU-1.
  
 6) M1.02: CLARIFY THE PURPOSE OF EF-1 IN THE WALL BY
 THE ELEVATOR AND INDICATE HOW THE FAN WAS SIZED-
 PROVIDE A CALCULATION.
  
 7) PLEASE CLARIFY WHAT TYPE OF "TREATMENT" IS PERFORMED
 IN THE VARIOUS ROOMS SHOWN ON THE PLAN SO A COMPLETE
 MECHANICAL REVIEW CAN BE ACCOMPLISHED.
  
 8) PROVIDE AN AIR BALANCE CALCULATION.
  
 9) PROVIDE CHILLED WATER AND CONDENSATE PIPING DETAILS-
 TYPE OF PIPING, TYPE OF INSULATION AND INSULATION
 THICKNESSES,
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  