Date |
Text |
2017-06-30 08:35:59 | 2ND REVIEW FBC-2014 MECHANICAL |
| PERMIT #17020366 |
| 6/30/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| THE RESUBMITTED PLANS DO NOT APPREAR TO BE CORRECTED |
| PER THE 1ST REVIEW COMMENTS. MANY OF THE DEFICIENCIES |
| STILL EXIST, AND NO NARRATIVE FROM THE ENGINEER WAS |
| SUBMITTED IN RESPONSE WHICH TYPICALLY HELPS TO CLARIFY |
| AND EXPEDITE THE REVIEW PROCESS. I AM REPRINTING THE |
| 1ST REVIEW COMMENTS BELOW. PLEASE NOTE THAT THE |
| BUILDING PLAN REVIEWER'S SECOND REVIEW COMMENTS ARE |
| STATING THAT THE RESUBMITTED PLANS ARE INDICATING A NEW |
| SECOND FLOOR WALL MUST BE CONSTRUCTED TO SEPARATE THE |
| ATRIUM FROM THE SECOND FLOOR LEVEL. THIS REQUIRED |
| REDESIGN WILL OBVIOUSLY IMPACT THE CURRENT HVAC DESIGN. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17020366 |
| 2/14/17 |
| |
| 1) SHEET M1.01: THE SUMMARY "WHOLE SYSTEM HEAT LOADS" |
| ARE INCOMPLETE- SEE SECTION C403.2.1 FBC-14 ENERGY |
| CONSERVATION AND PROVIDE CALCULATIONS IN ACCORDANCE |
| WITH ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N. SUMMARY |
| CALCULATIONS PER THE EXCEPTION MUST INCLUDE ITEMS 1-13, |
| BE PERFORMED FOR EACH ZONE, AND BE SUBMITTED ON A |
| SIGNED AND SEALED SUMMARY SHEET. |
| |
| 2) M1.01: PLEASE BREAKDOWN THE VENTILATION CALCULATIONS |
| FOR THE BEAUTY/NAIL SALON TO PROVIDE 50 CFM PER NAIL |
| TABLE AND 0.60 CFMS PER SF FOR THE SALON. THE CURRENT |
| PLAN APPEARS TO BE NON-COMPLIANT WITH ONLY THE EF-1 |
| FUNCTIONING IN THE AREA. |
| |
| 3) M1.01 & M1.02: THE PLAN INDICATES AIR IN THE BEAUTY |
| SALON IS BEING RECIRCULATED INTO OTHER ROOMS AND SPACES |
| WHICH IS PROHIBITED PER TABLE 403.3 FOOTNOTE B- PLEASE |
| CORRECT. |
| |
| 4) M1.01: EXHAUST VENTILATION IS REQUIRED FOR THE |
| SHOWER- SEE TABLE 403.3 AND PROVIDE A SYSTEM. |
| |
| 5) M1.01: INDICATE HOW OUTSIDE AIR IS BEING SUPPLIED TO |
| AHU-1. |
| |
| 6) M1.02: CLARIFY THE PURPOSE OF EF-1 IN THE WALL BY |
| THE ELEVATOR AND INDICATE HOW THE FAN WAS SIZED- |
| PROVIDE A CALCULATION. |
| |
| 7) PLEASE CLARIFY WHAT TYPE OF "TREATMENT" IS PERFORMED |
| IN THE VARIOUS ROOMS SHOWN ON THE PLAN SO A COMPLETE |
| MECHANICAL REVIEW CAN BE ACCOMPLISHED. |
| |
| 8) PROVIDE AN AIR BALANCE CALCULATION. |
| |
| 9) PROVIDE CHILLED WATER AND CONDENSATE PIPING DETAILS- |
| TYPE OF PIPING, TYPE OF INSULATION AND INSULATION |
| THICKNESSES, |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |