2017-02-24 12:52:34 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| COMMENTS: |
| |
| 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE |
| SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, |
| ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS |
| SYSTEMS, ETC. A NOTE WILL SUFFICE. |
| 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, |
| 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP |
| AND COMPLETIONS DOCUMENTS. |
| 3. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION |
| PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC |
| 107. |
| 4. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| VERBIAGE IN CODE. |
| 5. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405 SEE |
| VERBIAGE IN THE CODE REGARDING AUTOMATIC LIGHTING |
| CONTROLS AND MINIMUM LIGHTING DENSITIES. |
| 6. SHOW ON POWER AND LIGHTING LAYOUT, THE BRANCH |
| CIRCUIT NUMBERS ASSIGNED TO EACH OUTLET? FBC 107.3.5 |
| 7. PLANS ARE VERY VAGUE AND DEFICIENT; A COMPLETE |
| ELECTRICAL REVIEW CANNOT BE PERFORMED TO PROVIDE A |
| CHECKLIST TO DESIGNER OF RECORD WITH EVERY APPLICABLE |
| FBC, NFPA AND NEC PROVISIONS APPLICABLE TO THIS PROJECT |
| WHICH HAS MULTIPLE DEFICIENCIES. |
| 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| TO CONTACT ME SHOULD YOU HAVE ANY |
| |
| |