2017-02-15 11:31:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020366
 ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2(A)
 CONT: TBD
 TEL: 561-358-9909
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 15/ 2017
 ACTION: DENIED
  
 1) SHEET A-0.01 UNDER THE HEADING LIST THIS BUILDING
 TYPE TO BE A BUILDING TYPE IIA. PLEASE NOTE ABOVE THE
 1ST FLOOR LEVEL THIS HIGH RISE IS A R2 OCCUPANCY TYPE.
 PLEASE NOTE THIS IS A 20 STORY HIGH RISE, THE MINIMUM
 BUILDING TYPE REQUIRED WOULD BE TYPE IA SEE 2014 FBC-B
 TABLE 503.
  
 2) SHEET A-0.01 SHOWS AN EXISTING MEZZANINE OF 329 SQ.
 FT. AND AN ADDITIONAL 299 SQ. FT. ADDED TO THE
 MEZZANINE LEVEL TOTALING 628 SQ. FT. THE TOTAL SQ. FT.
 OF THE 1ST FLOOR IS GIVEN 1864 SQ. FT. OR 28.6 % OF THE
 FLOOR AREA.
  
 THIS IS NOT THE WAY TO FIGURE THE ALLOWABLE AREA OF
 MEZZANINES. THE SIZE OF THE MEZZANINE IS FIGURED NOT
 GREATER THAN 1/3 THE ROOM THEY ARE LOCATED (FBC-B
 505.2.1). SEE EXCEPTION # 2. THE AGGREGATE AREA OF
 MEZZANINES IN BUILDINGS AND STRUCTURES OF TYPE I OR II
 CONSTRUCTION SHALL BE NOT GREATER THAN ONE-HALF OF THE
 FLOOR AREA OF THE ROOM IN BUILDINGS AND STRUCTURES
 EQUIPPED THROUGHOUT WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1
 AND AN APPROVED EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 THE ENCLOSED AREA OF THE 1ST FLOOR DOES NOT COMMUNICATE
 WITH THE MEZZANINE AREA ARE NOT INCLUDED IN THE
 CALCULATING THE 1ST FLOOR AREA. THE TOTAL AREA OF THE
 1ST FLOOR AREA THAT COMMUNICATES WITH THE MEZZANINE
 LEVEL IS 833.25 SQ. FT.
 833.25 SQ. FT. X 0.33= 274.9725 SQ. FT.
 833.25 SQ. FT. X 0.50= 416.6250 SQ. FT.
 EXISTING MEZZANINE 329.0000 SQ. FT.
 WITH THE WALLS AS SHOWN ON THE 1ST FLOOR THE EXISTING
 MEZZANINE MAYBE AN ISSUE IF THERE IS NO ALARM IN
 COMPLIANCE WITH FBC-B 907.5.2.2.
 907.5.2.2 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS.
 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS REQUIRED BY
 THIS CODE SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH NFPA 72. THE OPERATION OF ANY AUTOMATIC FIRE
 DETECTOR, SPRINKLER WATERFLOW DEVICE OR MANUAL FIRE
 ALARM BOX SHALL AUTOMATICALLY SOUND AN ALERT TONE
 FOLLOWED BY VOICE INSTRUCTIONS GIVING APPROVED
 INFORMATION AND DIRECTIONS FOR A GENERAL OR STAGED
 EVACUATION IN ACCORDANCE WITH THE BUILDING?S FIRE
 SAFETY AND EVACUATION PLANS REQUIRED BY THE FLORIDA
 FIRE PREVENTION CODE. IN HIGH-RISE BUILDINGS, THE
 SYSTEM SHALL OPERATE ON A MINIMUM OF THE ALARMING
 FLOOR, THE FLOOR ABOVE AND THE FLOOR BELOW. SPEAKERS
 SHALL BE PROVIDED THROUGHOUT THE BUILDING BY PAGING
 ZONES. AT A MINIMUM, PAGING ZONES SHALL BE PROVIDED AS
 FOLLOWS:
 1. ELEVATOR GROUPS.
 2. EXIT STAIRWAYS.
 3. EACH FLOOR.
 4. AREAS OF REFUGE AS DEFINED IN SECTION 1002.1.
  
 2) SINCE THERE IS STRUCTURAL WORK BEING COMPLETED UNDER
 THIS PERMIT AND THIS BUILDING IS A 20 STORY HIGHRISE IT
 QUALIFIES AS A THRESHOLD BUILDING. THRESHOLD BUILDING /
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 FORMS E-MAILED TO: [email protected] 02/15/2017
 11:29AM
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) SHEET S-1.01 SHOWS A DETAIL FOR THE HELICAL PILE
 INSTALLATION. PLEASE PROVIDE THE SOILS ANALYSIS OF HOW
 THE PILE SIZE AND LENGTH OF PILE AND FREQUENCY OF
 INSTALLATION WAS ACHIEVED. 1803.5.2 QUESTIONABLE SOIL.
  
 4) SHEET S-1.01 SHOWS A DETAIL FOR THE HELICAL PILE
 INSTALLATION. THE ENGINEER OF RECORD STATES THE PILE
 ARE TO BE INSTALLED UNDER THE SUPERVISION OF AN
 ENGINEER WHO SPECIALIZES IN THE INSTALLATION OF HELICAL
 PILES AND WHO SHALL CERTIFY THEIR INSTALLATION AND
 CAPACITIES. PLEASE PROVIDE DOCUMENTATION.
 FBC-B 1810.3.1.5 HELICAL PILES. HELICAL PILES SHALL BE
 DESIGNED AND MANUFACTURED IN ACCORDANCE WITH ACCEPTED
 ENGINEERING PRACTICE TO RESIST ALL STRESSES INDUCED BY
 INSTALLATION INTO THE GROUND AND SERVICE LOADS.
  
 5) SHEET A-1.01 SHOWS AN EQUIPMENT CLOSET NEXT TO THE
 ELEVATOR SHAFT. PLEASE PROVIDE IF THIS IS THE EQUIPMENT
 ROOM FOR THE ELEVATOR. IF SO THE WALLS ARE SHOWN AS 1
 HOUR FIRE RATING, BUT THE DOORS # 11& 12 SHOW NO RATING
 SEE DOOR SCHEDULE THIS SHEET. SEE FBC-B 3006.4.
 OPENINGS IN THE FIRE BARRIERS SHALL BE PROTECTED WITH
 ASSEMBLIES HAVING A FIRE PROTECTION RATING NOT LESS
 THAN THAT REQUIRED FOR THE HOISTWAY ENCLOSURE DOORS.
 TABLE 716.5.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  