2017-02-15 11:31:31 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17020366 |
| ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2(A) |
| CONT: TBD |
| TEL: 561-358-9909 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. FEB. 15/ 2017 |
| ACTION: DENIED |
| |
| 1) SHEET A-0.01 UNDER THE HEADING LIST THIS BUILDING |
| TYPE TO BE A BUILDING TYPE IIA. PLEASE NOTE ABOVE THE |
| 1ST FLOOR LEVEL THIS HIGH RISE IS A R2 OCCUPANCY TYPE. |
| PLEASE NOTE THIS IS A 20 STORY HIGH RISE, THE MINIMUM |
| BUILDING TYPE REQUIRED WOULD BE TYPE IA SEE 2014 FBC-B |
| TABLE 503. |
| |
| 2) SHEET A-0.01 SHOWS AN EXISTING MEZZANINE OF 329 SQ. |
| FT. AND AN ADDITIONAL 299 SQ. FT. ADDED TO THE |
| MEZZANINE LEVEL TOTALING 628 SQ. FT. THE TOTAL SQ. FT. |
| OF THE 1ST FLOOR IS GIVEN 1864 SQ. FT. OR 28.6 % OF THE |
| FLOOR AREA. |
| |
| THIS IS NOT THE WAY TO FIGURE THE ALLOWABLE AREA OF |
| MEZZANINES. THE SIZE OF THE MEZZANINE IS FIGURED NOT |
| GREATER THAN 1/3 THE ROOM THEY ARE LOCATED (FBC-B |
| 505.2.1). SEE EXCEPTION # 2. THE AGGREGATE AREA OF |
| MEZZANINES IN BUILDINGS AND STRUCTURES OF TYPE I OR II |
| CONSTRUCTION SHALL BE NOT GREATER THAN ONE-HALF OF THE |
| FLOOR AREA OF THE ROOM IN BUILDINGS AND STRUCTURES |
| EQUIPPED THROUGHOUT WITH AN APPROVED AUTOMATIC |
| SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1 |
| AND AN APPROVED EMERGENCY VOICE/ALARM COMMUNICATION |
| SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2. |
| |
| THE ENCLOSED AREA OF THE 1ST FLOOR DOES NOT COMMUNICATE |
| WITH THE MEZZANINE AREA ARE NOT INCLUDED IN THE |
| CALCULATING THE 1ST FLOOR AREA. THE TOTAL AREA OF THE |
| 1ST FLOOR AREA THAT COMMUNICATES WITH THE MEZZANINE |
| LEVEL IS 833.25 SQ. FT. |
| 833.25 SQ. FT. X 0.33= 274.9725 SQ. FT. |
| 833.25 SQ. FT. X 0.50= 416.6250 SQ. FT. |
| EXISTING MEZZANINE 329.0000 SQ. FT. |
| WITH THE WALLS AS SHOWN ON THE 1ST FLOOR THE EXISTING |
| MEZZANINE MAYBE AN ISSUE IF THERE IS NO ALARM IN |
| COMPLIANCE WITH FBC-B 907.5.2.2. |
| 907.5.2.2 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS. |
| EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS REQUIRED BY |
| THIS CODE SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE |
| WITH NFPA 72. THE OPERATION OF ANY AUTOMATIC FIRE |
| DETECTOR, SPRINKLER WATERFLOW DEVICE OR MANUAL FIRE |
| ALARM BOX SHALL AUTOMATICALLY SOUND AN ALERT TONE |
| FOLLOWED BY VOICE INSTRUCTIONS GIVING APPROVED |
| INFORMATION AND DIRECTIONS FOR A GENERAL OR STAGED |
| EVACUATION IN ACCORDANCE WITH THE BUILDING?S FIRE |
| SAFETY AND EVACUATION PLANS REQUIRED BY THE FLORIDA |
| FIRE PREVENTION CODE. IN HIGH-RISE BUILDINGS, THE |
| SYSTEM SHALL OPERATE ON A MINIMUM OF THE ALARMING |
| FLOOR, THE FLOOR ABOVE AND THE FLOOR BELOW. SPEAKERS |
| SHALL BE PROVIDED THROUGHOUT THE BUILDING BY PAGING |
| ZONES. AT A MINIMUM, PAGING ZONES SHALL BE PROVIDED AS |
| FOLLOWS: |
| 1. ELEVATOR GROUPS. |
| 2. EXIT STAIRWAYS. |
| 3. EACH FLOOR. |
| 4. AREAS OF REFUGE AS DEFINED IN SECTION 1002.1. |
| |
| 2) SINCE THERE IS STRUCTURAL WORK BEING COMPLETED UNDER |
| THIS PERMIT AND THIS BUILDING IS A 20 STORY HIGHRISE IT |
| QUALIFIES AS A THRESHOLD BUILDING. THRESHOLD BUILDING / |
| FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY |
| BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| PLACE. |
| FORMS E-MAILED TO: [email protected] 02/15/2017 |
| 11:29AM |
| |
| 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| |
| 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| |
| 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| IN BLACK & WHITE.. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| CONCERNING SPECIAL INSPECTORS. |
| |
| 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| |
| 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| WALLS AND CEILINGS. |
| |
| 3) SHEET S-1.01 SHOWS A DETAIL FOR THE HELICAL PILE |
| INSTALLATION. PLEASE PROVIDE THE SOILS ANALYSIS OF HOW |
| THE PILE SIZE AND LENGTH OF PILE AND FREQUENCY OF |
| INSTALLATION WAS ACHIEVED. 1803.5.2 QUESTIONABLE SOIL. |
| |
| 4) SHEET S-1.01 SHOWS A DETAIL FOR THE HELICAL PILE |
| INSTALLATION. THE ENGINEER OF RECORD STATES THE PILE |
| ARE TO BE INSTALLED UNDER THE SUPERVISION OF AN |
| ENGINEER WHO SPECIALIZES IN THE INSTALLATION OF HELICAL |
| PILES AND WHO SHALL CERTIFY THEIR INSTALLATION AND |
| CAPACITIES. PLEASE PROVIDE DOCUMENTATION. |
| FBC-B 1810.3.1.5 HELICAL PILES. HELICAL PILES SHALL BE |
| DESIGNED AND MANUFACTURED IN ACCORDANCE WITH ACCEPTED |
| ENGINEERING PRACTICE TO RESIST ALL STRESSES INDUCED BY |
| INSTALLATION INTO THE GROUND AND SERVICE LOADS. |
| |
| 5) SHEET A-1.01 SHOWS AN EQUIPMENT CLOSET NEXT TO THE |
| ELEVATOR SHAFT. PLEASE PROVIDE IF THIS IS THE EQUIPMENT |
| ROOM FOR THE ELEVATOR. IF SO THE WALLS ARE SHOWN AS 1 |
| HOUR FIRE RATING, BUT THE DOORS # 11& 12 SHOW NO RATING |
| SEE DOOR SCHEDULE THIS SHEET. SEE FBC-B 3006.4. |
| OPENINGS IN THE FIRE BARRIERS SHALL BE PROTECTED WITH |
| ASSEMBLIES HAVING A FIRE PROTECTION RATING NOT LESS |
| THAN THAT REQUIRED FOR THE HOISTWAY ENCLOSURE DOORS. |
| TABLE 716.5. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |