2017-02-14 11:42:041ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020362
 2/14/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) M2.1: THE NEW FPT-11-12 APPEARS TO BE SUPPLYING 1400
 CFMS OF AIR, HOWEVER THE SCHEDULE ON M4.1 INDICATES A
 DESIGN AIRFLOW OF 900 CFMS- PLEASE CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER