Plan Review Notes For Permit 17020362 |
Permit Number |
17020362 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-14 11:42:04 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17020362 | | 2/14/17 | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR. | | | | 2) M2.1: THE NEW FPT-11-12 APPEARS TO BE SUPPLYING 1400 | | CFMS OF AIR, HOWEVER THE SCHEDULE ON M4.1 INDICATES A | | DESIGN AIRFLOW OF 900 CFMS- PLEASE CORRECT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|