2017-03-07 10:31:42PROVISO
  
 1) PROVIDE FAULT CURRENT CALCULATION AND SIGNAGE FOR
 THE NEW TRANSFORMER. PER 110.24 (A)(B)
  
 2) PROVIDE INTERIOR POWER ALLOWANCES PER FBC EC 405.5.2
  
 3) PROVIDE THIS INFORMATION PRIOR TO THE FINAL
 INSPECTION.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II