Plan Review Notes
Plan Review Notes For Permit 17020334
Permit Number 17020334
Review Stop G
Sequence Number 1
Notes
Date Text
2017-02-10 04:51:551) THE SUBMITTED SPECIFICATION SHEET FOR THE POOL
 HEATER IS PRINTED IN A FOREIGN LANGUAGE. I CANNOT
 REVIEW DOCUMENTS THAT I CANNOT READ. SUBMIT TWO COPIES
 OF THE MANUFACTURER'S SPECIFICATIONS PRINTED IN THE
 ENGLISH LANGUAGE. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE POOL HEATER SHALL COMPLY WITH THE 2014
 FBC-ENERGY CODE SEC. R403.9, R403.9.1, R403.9.
 3) HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH A VAPOR
 - RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT
 LOSS.FBC-ENERGY 403.9.3.
 4) SUBMIT INFORMATION ON THE TYPE OF PIPE FOR THE
 RISERS COMING OFF THE PE PIPE. SHOW THE PIPE SIZE, TYPE
 OF PIPE MATERIAL, AND SUBMIT THE SIZING TABLE USED FOR
 THESE SECTIONS OF PIPE AT THE METER AND AT THE POOL
 HEATER.
 5) INDICATE ON THE PLAN IF THE POOL HEATER IS THE ONLY
 GAS APPLIANCE ON THIS SYSTEM. IF NOT, SUBMIT A COMPLETE
 GAS RISER SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE
 DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, THE BTU
 LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE
 OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. THESE
 REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. WPB AMEND.
 TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  