Plan Review Notes
Plan Review Notes For Permit 17020313
Permit Number 17020313
Review Stop P
Sequence Number 1
Notes
Date Text
2017-02-10 03:10:541) IS THE NEW TANKLESS WATER HEATER REPLACING AN
 EXISTING TANKLESS WATER HEATER OR IS THE TANKLESS
 REPLACING A TANK TYPE WATER HEATER? NOTE THIS ON THE
 PLAN.IF A TANK TYPE WATER HEATER IS BEING REPLACED WITH
 THE TANKLESS, AN UPGRADE TO THE ELECTRIC MAY BE
 REQUIRED WHICH WILL REQUIRE A SEPARATE PERMIT. WPB
 AMEND. TO FBC SEC.107.2.1.
 2) IS THE TANKLESS WATER HEATER BEING INSTALLED ON THE
 INTERIOR OR EXTERIOR OF THE STRUCTURE? SUBMIT TWO
 COPIES OF A HOUSE PLAN SHOWING THE LOCATION OF THE
 TANKLESS WATER HEATER AND THE LOCATION OF ANY OPERABLE
 DOORS OR WINDOWS. THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND DRAWN. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT 2 COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE
 TANKLESS WATER HEATER. WPB AMEND. TO FBC SECS.
 102.1,107.2.1.
 4) CLEARLY IDENTIFY ON THE SANITARY RISER DIAGRAM WHAT
 PIPING IS BEING REPLACED. IS ALL THE UNDERGROUND/UNDER
 SLAB PIPING BEING REPLACED INCLUDING THE STACKS?
 5) IF THE AREA UNDER THE SLAB IS TO BE TUNNELLED TO
 GAIN ACCESS TO THE EXISTING SANITARY LINES, THEN THE
 FOLLOWING SHALL BE ADHERED TO:
  
 PLUMBING REPAIR TUNNEL WORK
  
 A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE
 SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO
 EXISTING PIPING, HOW THE NEW PIPE WILL BE SUPPORTED,
 THE TYPE OF ADAPTERS USED FOR THE CONNECTIONS TO
 EXISTING PIPE, AND THE LOCATIONS OF REQUIRED CLEANOUTS.
 DETAILS AND BACKFILLING PROCEDURES SHALL BE SUBMITTED
 THAT CLEARLY SHOW HOW THE STRUCTURAL INTEGRITY OF THE
 CONCRETE SLAB WILL BE MAINTAINED DURING EXCAVATION AND
 BACKFILLING. STRUCTURAL FOAM IS NOT PERMITTED BELOW
 GROUND PER THE FLORIDA BUILDING CODE, RESIDENTIAL,
 SECTION 318 AND THE FLORIDA BUILDING CODE, BUILDING,
 SECTION 26. A SIGNED AND SEALED LETTER FROM AN ENGINEER
 SHALL BE SUBMITTED FOR FINAL INSPECTION STATING THAT
 THE STRUCTURAL INTEGRITY OF THE EXISTING SLAB HAS NOT
 BEEN COMPROMISED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  