2017-02-14 08:01:05 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | CHECKLIST. . | | CODE: FBC 5TH EDITION (2014) | | | | ORIGINAL COMMENTS: | | 1- FLAT ROOF NOA 14-1030.02 SUBMITTED; | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL, 5TH | | EDITION (2014). | | | | B) IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL FOR | | ALL ROOF ZONES, THEN NEED TO PROVIDE SIGNED AND SEALED | | RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION | | #7 ON LAST PAGE OF NOA SUBMITTED. | | NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NO BE | | USED IF THE DESIGN PRESSURES ARE TOO LOW. GENERAL | | LIMITATION $9 DOESN'T ALLOW RAS 117 CALCULATIONS. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. CONTRACTOR RE-SUBMITTED | | SHINGLES NOA 13-0419.04 AND NOA 12-0228.18 FOR ROOF | | TILE ADHESIVES. THE NOA FOR SHINGLES WAS ALREADY | | SUBMITTED AT TIME OF PERMIT APPLICATION. THERE ARE NO | | ROOF TILES ON THIS PROJECT. CONTRACTOR NEED TO ADDRESS | | ORIGINAL COMMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|