2017-02-08 17:34:10 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17020286 |
| W. P. B. PERMIT: 16081292 |
| ADD: 201 NARCISSUS ST. SUITE # 905/906 |
| CONT: PHILIP E. JOHNSON, INC. |
| TEL: 561-366-1034 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 08/ 2017 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED SALES BROCHURE FOR SAM 90 IS JUST THAT |
| A SALES BROCHURE. PLEASE NOTE THE CITY REQUIRES THE |
| ACTUAL TEST. THE TECHNICAL DATA IN THE BROCHURE STATES |
| THE IIC VALE OF 70 AND STC VALUE OF 67, THEY DO NOT |
| STATE THE SLAB THICKNESS AND THE TEST WAS PREFORMED |
| WITH A DROP CEILING FULL OF INSULATION. |
| IF YOU ARE LOOKING FOR THE USE OF THIS PRODUCT THE CITY |
| DOES HAVE INTERTEK TEST REPORTS, TESTED ON A 5 INCH |
| CONCRETE SLAB, NO DROP CEILING WITH A STC OF 54 AND IIC |
| OF 51 FOR SUPER SAM-125 UNDERLAYMENT BUT NO TEST RESULT |
| FOR FLAME SPREAD AND SMOKE DEVELOPMENT. |
| SEE THE ACTUAL REQUIREMENTS BELOW. |
| |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2014) |
| FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| JAMES A. WITMER BN, PX, CBO |