Plan Review Notes
Plan Review Notes For Permit 17020286
Permit Number 17020286
Review Stop B
Sequence Number 1
Notes
Date Text
2017-02-08 17:34:10BUILDING PLAN REVIEW
 W. P. B. REVISION: 17020286
 W. P. B. PERMIT: 16081292
 ADD: 201 NARCISSUS ST. SUITE # 905/906
 CONT: PHILIP E. JOHNSON, INC.
 TEL: 561-366-1034
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 08/ 2017
 ACTION: DENIED
  
 1) THE SUBMITTED SALES BROCHURE FOR SAM 90 IS JUST THAT
 A SALES BROCHURE. PLEASE NOTE THE CITY REQUIRES THE
 ACTUAL TEST. THE TECHNICAL DATA IN THE BROCHURE STATES
 THE IIC VALE OF 70 AND STC VALUE OF 67, THEY DO NOT
 STATE THE SLAB THICKNESS AND THE TEST WAS PREFORMED
 WITH A DROP CEILING FULL OF INSULATION.
 IF YOU ARE LOOKING FOR THE USE OF THIS PRODUCT THE CITY
 DOES HAVE INTERTEK TEST REPORTS, TESTED ON A 5 INCH
 CONCRETE SLAB, NO DROP CEILING WITH A STC OF 54 AND IIC
 OF 51 FOR SUPER SAM-125 UNDERLAYMENT BUT NO TEST RESULT
 FOR FLAME SPREAD AND SMOKE DEVELOPMENT.
 SEE THE ACTUAL REQUIREMENTS BELOW.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  