Plan Review Notes
Plan Review Notes For Permit 17020285
Permit Number 17020285
Review Stop B
Sequence Number 2
Notes
Date Text
2017-02-13 15:59:08RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014)
  
 1- NEW FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R19
 SUBMITTED:
 SELECTED ASSEMBLY W52 DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS (2 COPIES) AS REQUIRED BY NOTE #11 TO MEET
 THE DESIGN PRESSURES REQUIRED BY SEC. R301.1
 FBC-RESIDENTIAL FOR THE CORNER AREAS.
  
 NOTE: THERE ARE TWO DIFFERENT TYPES OF ROOF PROPOSED
 FOR THIS PROJECT. THERE IS ONE INSULATED ROOF SYSTEM
 (W-52) AND ONE NON-INSULATED ROOF SYSTEM (W-106). THE
 INSULATED ROOF SYSTEM NEEDS THE RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES FOR ROOF ZONE #3. ACCORDING
 TO TABLE R301.2(2) -RESIDENTIAL THE CORNER PRESSURES
 FOR CORNER AREA FOR A ONE STORY BUILDING IS -95.7PSF.
 THE NON-INSULATED ROOF SYSTEM (W-106) IS OK BECAUSE THE
 DESIGN PRESSURES ARE HIGH ENOUGH TO COVER ALL ROOF
 ZONES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  