2017-03-23 10:50:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF PRODUCT APPROVALS, THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD, FOR THE GREENHECK EXHAUST FAN THAT SHOW IT
 MEETS REQUIRED WIND DESIGN PRESSURES. FBC 107.3.4.1
  
 2) SHOW COMPLIANCE WITH FBCR-M1506.2 M1506.2 EXHAUST
 OPENINGS. AIR EXHAUST OPENINGS SHALL TERMINATE NOT LESS
 THAN 3 FEET (914 MM) FROM PROPERTY LINES; 3 FEET (914
 MM) FROM OPERABLE AND NONOPERABLE OPENINGS INTO THE
 BUILDING AND 10 FEET (3048 MM) FROM MECHANICAL AIR
 INTAKES EXCEPT WHERE THE OPENING IS LOCATED 3 FEET (914
 MM) ABOVE THE AIR INTAKE. OPENINGS SHALL COMPLY WITH
 SECTIONS R303.5.2 AND R303.6.
  