Plan Review Notes For Permit 17020283 |
Permit Number |
17020283 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-23 10:50:29 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF PRODUCT APPROVALS, THAT HAVE BEEN | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD, FOR THE GREENHECK EXHAUST FAN THAT SHOW IT | | MEETS REQUIRED WIND DESIGN PRESSURES. FBC 107.3.4.1 | | | | 2) SHOW COMPLIANCE WITH FBCR-M1506.2 M1506.2 EXHAUST | | OPENINGS. AIR EXHAUST OPENINGS SHALL TERMINATE NOT LESS | | THAN 3 FEET (914 MM) FROM PROPERTY LINES; 3 FEET (914 | | MM) FROM OPERABLE AND NONOPERABLE OPENINGS INTO THE | | BUILDING AND 10 FEET (3048 MM) FROM MECHANICAL AIR | | INTAKES EXCEPT WHERE THE OPENING IS LOCATED 3 FEET (914 | | MM) ABOVE THE AIR INTAKE. OPENINGS SHALL COMPLY WITH | | SECTIONS R303.5.2 AND R303.6. | | |
|