Plan Review Notes
Plan Review Notes For Permit 17020283
Permit Number 17020283
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-08 08:33:29INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE LABEL GARAGE DOOR OPENER RECEPTACLES TO BE
 GFCI PROTECTED PER FBC RES E3902.2. READILY ACCESSIBLE.
 2. CLARIFY AS LOADS FOR THE CAR LIFT AND STORAGE LIFT
 ARE NOT SHOWN ON CALCULATED PANEL LOADS.
 3. GENERAL NOTE TO INDICATE REQUIRED SEPARATE PERMIT
 FOR GENERATOR INSTALLATION. A COMPLETE ELECTRICAL
 GENERATOR PACKAGE WILL NEED TO BE SUBMITTED AT THAT
 TIME. FBC 107.3.5
 4. PROVIDE A NOTE TO SHOW REQUIRED TAMPER RESISTANT
 RECEPTACLES PER FBC RES E4002.14
 5. PLEASE CLARIFY THE ATS SHOWN ON GARAGE WALL, AS
 RISER INDICATES DIFFERENT LOCATION AT CABANA. IS THIS
 THE PROPOSED LOCATION FOR THE PARALLELING GENERATOR
 EQUIPMENT? IF SO LABEL ACCORDINGLY.
 6. ZONING COMMENTS WILL NEED TO BE ADDRESSED PRIOR TO
 AN ELECTRICAL APPROVAL.
 7. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.