2017-03-23 19:00:46 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PROPOSED DETACHED GARAGE IS LOCATED IN A SPECIAL |
| FLOOD HAZARD AREA (SFHA) ( A5 ) WITH A BASE FLOOD |
| ELEVATION OF 7' NGVD. THE CITY OF WEST PALM BEACH HAS A |
| REQUIRED 1' FREEBOARD. THEREFORE THE GARAGE IS REQUIRED |
| TO HAVE THE LOWEST FINISH FLOOR ELEVATION AT 8' NGVD. |
| ALTERNATELY, THE GARAGE CAN BE BELOW THE BFE IF IT IS |
| USED SOLELY FOR PARKING OF VEHICLES OR STORAGE AND |
| DESIGNED WITH FLOOD OPENINGS. ALL EQUIPMENT AND |
| MATERIALS THAT ARE SUBJECT TO FLOOD DAMAGE IS REQUIRED |
| TO BE AT OR ABOVE THE 8' NGVD ELEVATION. PROVIDE |
| DRAWINGS THAT DETAIL HOW THIS WILL BE ADDRESSED. |
| FBC-R322 AND CITY FLOOD ORDINANCE |
| |
| 2) SPECIFY THE ELEVATIONS IN NGVD OF THE GARAGE AND ALL |
| EQUIPMENT ON THE PLANS. FBC-R322 AND CITY FLOOD |
| ORDINANCE |
| |
| 3) SUBMIT PRE CONSTRUCTION ELEVATION CERTIFICATES TO |
| SHOW PROPOSED ELEVATIONS. FBC-R322 AND CITY FLOOD |
| ORDINANCE |
| |
| 4) ADDRESS THE ZONING COMMENTS FOR RECORDING OF THE |
| RE-PLAT. FBC 107.2.5 |
| |
| 5) A SEPARATE PERMIT, APPLICATION AND REVIEW IS |
| REQUIRED FOR THE GENERATORS. FBC105.1 |
| |
| 6) THIS STRUCTURE IS LOCATED IN EXPOSURE D RATHER THAN |
| C. PLEASE CORRECT. FBC-R301.2.1.4.3 |
| |
| 7) THE WIND DESIGN DATA ON SHEET S.01 CONTAINS SOME |
| ERRORS. THIS BUILDING IS NOT A PARTIALLY ENCLOSED |
| STRUCTURE. IT IS AN ENCLOSED STRUCTURE. THIS BUILDING |
| IS NOT TWO STORY, IT IS ONE STORY. THE MEAN ROOF HEIGHT |
| IS NOT 23 FEET, THE EAVE HEIGHT IS NOT 20 FEET AND THE |
| RIDGE HEIGHT IS NOT 26 FEET. PLEASE CORRECT. FBC-R |
| 301.2.1 |
| |
| 8) UPDATE THE MASONRY STANDARDS THAT ARE REFERENCED ON |
| SHEET S.01. ACI 318 - 11 AND ACI 530 - 11 ARE THE |
| EDITIONS REFERENCED IN THE 2014 FBC-R CHAPTER 46. |
| |
| 9) PROVIDE A BUCK DETAIL FOR THE OUTSWING SIDE HINGED |
| GARAGE DOOR. FBC-R612.7.2.1 |
| |
| 10) PROVIDE STRUCTURAL DETAILS FOR THE ALUMINUM PERGOLA |
| THAT IS ATTACHED TO THE FRONT OF THE GARAGE. FBC |
| 107.2.1 & FBC-R301.1 |
| |
| 11) PROVIDE THE MANUFACTURER'S SPECIFICATIONS AND |
| LISTING INFORMATION FOR THE MOTORIZED STORAGE LIFT. |
| SPECIFY WHERE IT WILL BE LOCATED, WHAT IT'S LOAD |
| LIMITATIONS ARE AND SHOW THAT THE TRUSSES OR OTHER |
| STRUCTURAL MEMBERS TO WHICH IT WILL BE ATTACHED ARE |
| CAPABLE OF SAFELY SUPPORTING THE LOADS. FBC 107.2.1 & |
| FBC-R301.1 |
| |
| 12) SHOW COMPLIANCE WITH FBC-R302.1 AND TABLE |
| R302.1(1). THE 1' 6" SOFFIT PROJECTION IS LESS THAN 5 |
| FEET FROM THE PROPERTY AND IS REQUIRED TO HAVE A |
| MINIMUM FIRE-RESISTANCE RATING OF 1 HOUR ON THE |
| UNDERSIDE AND NO VENT OPENINGS. |
| |
| 13) IT APPEARS FROM THE WALL SECTIONS ON THE PLANS THAT |
| THIS BUILDING IS DESIGNED TO HAVE AN UN-VENTED ATTIC |
| WHICH WOULD NOT REQUIRE ATTIC VENTS IN THE SOFFITS. |
| PLEASE CLARIFY. FBC-R806.5 |
| |
| 14) NOTE PS-5 ON SHEET S.01 SPECIFIES THE SOFFIT |
| SHEATHING TO BE 5/8" PLYWOOD AND THE DETAILS ON THE |
| SECTIONS ON A.03 SHOW WIRE LATH AND STUCCO. PLEASE |
| CLARIFY. FBC 107.2.1 |
| |
| 15) SUBMIT TWO SETS OF PRODUCT EVALUATIONS WITH |
| INSTALLATION INSTRUCTIONS FOR THE SPRAY FOAM INSULATION |
| THAT WILL BE INSTALLED. FBC-R316 |
| |
| 16) SPECIFY THE METHOD OF ATTACHMENT (TYPE AND NUMBER |
| OF FASTENERS) THAT WILL BE USED TO INSTALL THE CONCRETE |
| ROOF TILE AND SHOW THAT IT WILL MEET WINDLOAD |
| REQUIREMENTS. IF AN ADHESIVE WILL BE USED, THEN SUBMIT |
| TWO SETS OF PRODUCT APPROVALS FOR THE ADHESIVE. |
| FBC-R905.3.7 |
| |
| 17) THE VALUATION HAS BEEN ADJUSTED FROM $35,000.00 TO |
| 44,864.00 BASED ON THE LATEST ICC VALUATION DATA. FBC |
| 109.3 |
| |
| 18) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |