2017-02-15 14:37:23 | 600 OKEECHOBEE BOULEVARD |
| TRACKING #17020270 |
| PERMIT #16090562 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| REVISED DRAWINGS DO NOT SHOW A PROPOSED 19'X19' CANOPY |
| (FIRE SPRINKLER PROTECTION OR INTUMESCENT PAINT). |
| |
| PLANS INDICATE A 72" TALL WOOD STORAGE STRUCTURE |
| ADJACENT TO THE GRILL. THIS STORAGE UNIT WILL NEED TO |
| BE NON-COMBUSTIBLE OR RELOCATED. |
| |
| |
| FROM THE EMAIL CHAIN 02/14/17: |
| MY INTERPRETATION IS THAT THE 10 FEET APPLIES TO THE |
| HORIZONTAL (TRIANGLE SIDE B) DISTANCE. FOR THE REASON |
| BEING THAT OVERHEAD STRUCTURES ARE NOT PERMITTED AT ALL |
| EVEN IF THEY WERE LOCATED 10 FEET ABOVE THE HEAT SOURCE |
| PER NFPA 1. WITH THAT BEING SAID, I APPRECIATE THE OUT |
| OF THE BOX THOUGHT PROCESS AND UTILIZING THE |
| PYTHAGOREAN THEOREM. IS THE STRUCTURAL COLUMN HOLDING |
| UP THE NEW TRELLIS/ROOF NON-COMBUSTIBLE? IF IT IS, I |
| WOULD CONSIDER ALLOWING YOUR CURRENT DISTANCES BE |
| UTILIZED IF WE CAN APPLY A LISTED INTUMESCENT PAINT OR |
| SIMILAR. LET ME KNOW YOUR THOUGHTS. WESLEY JOLIN |
| |
| FOR A BETTER UNDERSTANDING OF WHAT I AM REQUESTING |
| BELOW IS AN EMAIL FROM THE CLIENT INTERPRETING HOW THE |
| DISTANCE IS CALCULATED FROM THE GRILL TO THE EDGE OF |
| CANOPY. PLEASE ADVISE. HERE IS THE CANOPY LAID OUT AS |
| PER THE 19?X19? OVERALL DIMENSIONS. AS YOU CAN SEE IF |
| WE SHIFT THE CANOPY 10? AWAY FROM THE GRILL THE CANOPY |
| WILL NOT BE CENTERED OVER THE 2 COLUMNS. THE CANOPY |
| WOULD HAVE TO GET SMALLER SO IT WILL HAVE A SYMMETRICAL |
| LOOK. PLEASE ADVISE. |
| JONATHAN L. UZCATEGUI, LEED AP BD+C |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |