Plan Review Notes
Plan Review Notes For Permit 17020270
Permit Number 17020270
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-02-15 14:37:23600 OKEECHOBEE BOULEVARD
 TRACKING #17020270
 PERMIT #16090562
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVISED DRAWINGS DO NOT SHOW A PROPOSED 19'X19' CANOPY
 (FIRE SPRINKLER PROTECTION OR INTUMESCENT PAINT).
  
 PLANS INDICATE A 72" TALL WOOD STORAGE STRUCTURE
 ADJACENT TO THE GRILL. THIS STORAGE UNIT WILL NEED TO
 BE NON-COMBUSTIBLE OR RELOCATED.
  
  
 FROM THE EMAIL CHAIN 02/14/17:
 MY INTERPRETATION IS THAT THE 10 FEET APPLIES TO THE
 HORIZONTAL (TRIANGLE SIDE B) DISTANCE. FOR THE REASON
 BEING THAT OVERHEAD STRUCTURES ARE NOT PERMITTED AT ALL
 EVEN IF THEY WERE LOCATED 10 FEET ABOVE THE HEAT SOURCE
 PER NFPA 1. WITH THAT BEING SAID, I APPRECIATE THE OUT
 OF THE BOX THOUGHT PROCESS AND UTILIZING THE
 PYTHAGOREAN THEOREM. IS THE STRUCTURAL COLUMN HOLDING
 UP THE NEW TRELLIS/ROOF NON-COMBUSTIBLE? IF IT IS, I
 WOULD CONSIDER ALLOWING YOUR CURRENT DISTANCES BE
 UTILIZED IF WE CAN APPLY A LISTED INTUMESCENT PAINT OR
 SIMILAR. LET ME KNOW YOUR THOUGHTS. WESLEY JOLIN
  
 FOR A BETTER UNDERSTANDING OF WHAT I AM REQUESTING
 BELOW IS AN EMAIL FROM THE CLIENT INTERPRETING HOW THE
 DISTANCE IS CALCULATED FROM THE GRILL TO THE EDGE OF
 CANOPY. PLEASE ADVISE. HERE IS THE CANOPY LAID OUT AS
 PER THE 19?X19? OVERALL DIMENSIONS. AS YOU CAN SEE IF
 WE SHIFT THE CANOPY 10? AWAY FROM THE GRILL THE CANOPY
 WILL NOT BE CENTERED OVER THE 2 COLUMNS. THE CANOPY
 WOULD HAVE TO GET SMALLER SO IT WILL HAVE A SYMMETRICAL
 LOOK. PLEASE ADVISE.
 JONATHAN L. UZCATEGUI, LEED AP BD+C
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  