Plan Review Notes For Permit 17020233 |
Permit Number |
17020233 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-06-20 10:45:10 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW COMMENTS: | | | | 1. PROVIDE CLARIFICATION FOR SEVICE. FROM GOOGLE | | STREETVIEW, IT APPEARS THAT THIS IS AN OVERHEAD | | SERVICE. WILL THIS NOW BE UNDERGROUND? TYPICALLY, FPL | | DOES NOT PROVIDE THE UNDERGROUND CONDUCTORS TO THE | | HANDHOLE. IF SO, PLEASE SPECIFY THE SIZING OF SERVICE | | CONDUCTORS. NEC 230.23 OR 230.31; FBC RE3602.1 | | 2. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | CIRCUIT. NEC 250.32; FBC RE3607.3 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|