2017-06-20 10:45:10CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE CLARIFICATION FOR SEVICE. FROM GOOGLE
 STREETVIEW, IT APPEARS THAT THIS IS AN OVERHEAD
 SERVICE. WILL THIS NOW BE UNDERGROUND? TYPICALLY, FPL
 DOES NOT PROVIDE THE UNDERGROUND CONDUCTORS TO THE
 HANDHOLE. IF SO, PLEASE SPECIFY THE SIZING OF SERVICE
 CONDUCTORS. NEC 230.23 OR 230.31; FBC RE3602.1
 2. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  