2017-05-19 06:56:36 
 1.) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. 2ND
 REQUEST.
 2) SHOW THE PIPE SIZE SUPPLYING THE POOL HEATER
 DOWNSTREAM OF THE REGULATOR.
 3) SHOW THE PIPE SIZE SUPPLYING THE TANKLESS WATER
 HEATER.
 4) A SHUTOFF VALVE SHALL BE LOCATED IMMEDIATELY AHEAD
 OF EACH REGULATOR. (SEE POOL HEATER) FBCR SEC.G2420.4.
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC.107.2.1. PLEASE BE AWARE
 THAT MOST MANUFACTURER'S REQUIRE 4 FEET FROM OPERABLE
 DOORS AND WINDOWS FOR OUTDOOR UNITS. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  