2017-02-10 10:01:14PLEASE PROVIDE CLARITY AS TO THE SCOPE OF WORK
 PROPOSED. AC'S ARE SAID TO BE EXISTING BUT NEW WORK IS
 SHOWN. ARE YOU TAPPING THE LINE FEEDERS GUTTER AS SHOWN
 ON ONE LINE. PLEASE CLARIFY INTENT OF INSTALLATION.
  
 VAL PEREZ
 *6717