2017-03-13 15:40:40 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| CODE: FBC, 5TH EDITION (2014). |
| |
| NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE |
| REQUIRED DURING CONSTRUCTION. |
| |
| 1- ACCORDING TO THE FLOOD INSURANCE RATE MAP (FIRM) |
| COMMUNITY-PANEL NUMBER 120229 0020 B EFFECTIVE MARCH 1, |
| 1979 THE PROPOSED ADDITION WILL PLACE THE HOUSE IN |
| FLOOD ZONE A5. THE ADDITION AND THE EXISTING HOUSE NEED |
| TO COMPLY WITH THE REQUIREMENTS OF SEC. 1103.5 |
| FBC-EXISTING BUILDING, 5TH EDITION (2014). SHOW |
| COMPLIANCE WITH SEC. R322 FBC-RESIDENTIAL, 5TH EDITION |
| (2014). COORDINATE WITH ITEM #2 BELOW. NOTE: ANY SPACE |
| BELOW THE 7'-6" FINISH FLOOR ELEVATION NEEDS TO COMPLY |
| WITH THE FLOOD RESISTANT CONSTRUCTION OF SEC. R322 |
| FBC-RESIDENTIAL, INCLUDING FLOOD VENTS. |
| |
| 2- PROVIDE SURVEY (2 COPIES) SHOWING THE EXISTING HOUSE |
| FINISH FLOOR ELEVATION AND THE PROPOSED ADDITION |
| FINISHED FLOOR ELEVATION AS REQUIRED BY SEC. |
| 107.3.5.3(8) CITY AMENDMENTS. |
| |
| 3- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY |
| SEC. R401.4 FBC-RESIDENTIAL. |
| |
| 4- SPECIFY SIZE OF NEW ATTIC ACCESS SHOWN IN THE NEW |
| MATER BEDROOM AREA. SEC. R807 FBC-RESIDENTIAL. |
| |
| 5- SPECIFY CARBON MONOXIDE ALARMS WITHIN 10' OF EACH |
| BEDROOM, INCLUDING THE EXISTING BEDROOMS AS REQUIRED BY |
| SEC. R315 FBC-RESIDENTIAL. |
| |
| 6- CLARIFY WHY SUBMITING FLORIDA PRODUCT APPROVAL |
| FL17176-R0 FOR SLIDING GLASS DOORS?. THERE ARE NO |
| SLIDING GLASS DOORS SHOWN ON PLANS. IN ADDITION, THIS |
| FLORIDA PRODUCT APPROVAL IS FOR THE 2010 FBC CODE |
| VERSION. CURRENT CODE VERSION IS THE 2014 FBC. CLARIFY |
| AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 7- ARCHITECT OF RECORD TO SPECIFY ROOF TILE FASTENING |
| AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| SPECIFYING SCREWS, THEN SPECIFY SIZE AN NUMBER OF |
| SCREWS. IF SPECIFYING ADHESIVE, THEN PRODUCT APPROVAL |
| IS REQUIRED. |
| |
| 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF |
| RECORD. NOTE: SEE ROOF TILE PRODUCT APPROVAL FOR LISTED |
| ADHESIVES. |
| |
| B) MULLIONS AS SHOWN ON PLANS FOR DOORS AND WINDOWS. |
| NOTE: SPECIFY MULLION SIZE AND FASTENERS TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| C) FRENCH DOORS AS SHOWN ON PLANS. |
| |
| D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| FRAMING PLANS, WALL DETAILS AND TRUSS ANCHOR SCHEDULE. |
| . PROVIDE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING |
| THE SPECIFIED CONNECTOR OR ARCHITECT TO LIST ALL THE |
| FLORIDA PRODUCT APPROVAL NUMBERS NEXT TO EACH SPECIFIED |
| CONNECTOR. NOTE: FLORIDA PRODUCT APPROVAL FL474 |
| SPECIFIED ON THE TRUSS ANCHOR SCHEDULE NEEDS TO BE |
| UPDATED. NEED THE CURRENT 2014 FBC APPROVAL. |
| |
| 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE |
| PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. NOTE: PLEASE PLACE REVIEW STAMP ON THE |
| FRONT PAGE OF THE PRODUCT APPROVALS NOT ON THE BACK. |
| THIS IS FOR PROPER SCANNING OF DOCUMENTS FOR RECORDS |
| RETENTION PURPOSES. |
| |
| 10- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE FOAM |
| INSULATION SPECIFIED ON PLANS SHOWING COMPLIANCE WITH |
| SEC. R316 FBC-RESIDENTIAL. |
| |
| 11- ENERGY CALCULATIONS SUBMITTED. NOTE: THIS IS A |
| CONTRIBUTING HISTORIC HOUSE. ENERGY CALCULATIONS ARE |
| NOT REQUIRED, BUT IF CONTRACTOR WANTS TO SUBMITT THEM, |
| THEN REVISE AS REQUIRED: |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| B) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION |
| SHOWN ON PAGE 3 OF 4 TO MATCH PLANS SUBMITTED. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| NOTE: LABELS FOR DOORS AND WINDOWS SHOWING THE U-FACTOR |
| AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE |
| THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD |
| DRAWINGS FOR REFERENCE. |
| |