Plan Review Notes
Plan Review Notes For Permit 17020152
Permit Number 17020152
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-13 15:40:40RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE
 REQUIRED DURING CONSTRUCTION.
  
 1- ACCORDING TO THE FLOOD INSURANCE RATE MAP (FIRM)
 COMMUNITY-PANEL NUMBER 120229 0020 B EFFECTIVE MARCH 1,
 1979 THE PROPOSED ADDITION WILL PLACE THE HOUSE IN
 FLOOD ZONE A5. THE ADDITION AND THE EXISTING HOUSE NEED
 TO COMPLY WITH THE REQUIREMENTS OF SEC. 1103.5
 FBC-EXISTING BUILDING, 5TH EDITION (2014). SHOW
 COMPLIANCE WITH SEC. R322 FBC-RESIDENTIAL, 5TH EDITION
 (2014). COORDINATE WITH ITEM #2 BELOW. NOTE: ANY SPACE
 BELOW THE 7'-6" FINISH FLOOR ELEVATION NEEDS TO COMPLY
 WITH THE FLOOD RESISTANT CONSTRUCTION OF SEC. R322
 FBC-RESIDENTIAL, INCLUDING FLOOD VENTS.
  
 2- PROVIDE SURVEY (2 COPIES) SHOWING THE EXISTING HOUSE
 FINISH FLOOR ELEVATION AND THE PROPOSED ADDITION
 FINISHED FLOOR ELEVATION AS REQUIRED BY SEC.
 107.3.5.3(8) CITY AMENDMENTS.
  
 3- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 FBC-RESIDENTIAL.
  
 4- SPECIFY SIZE OF NEW ATTIC ACCESS SHOWN IN THE NEW
 MATER BEDROOM AREA. SEC. R807 FBC-RESIDENTIAL.
  
 5- SPECIFY CARBON MONOXIDE ALARMS WITHIN 10' OF EACH
 BEDROOM, INCLUDING THE EXISTING BEDROOMS AS REQUIRED BY
 SEC. R315 FBC-RESIDENTIAL.
  
 6- CLARIFY WHY SUBMITING FLORIDA PRODUCT APPROVAL
 FL17176-R0 FOR SLIDING GLASS DOORS?. THERE ARE NO
 SLIDING GLASS DOORS SHOWN ON PLANS. IN ADDITION, THIS
 FLORIDA PRODUCT APPROVAL IS FOR THE 2010 FBC CODE
 VERSION. CURRENT CODE VERSION IS THE 2014 FBC. CLARIFY
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- ARCHITECT OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AN NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN PRODUCT APPROVAL
 IS REQUIRED.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. NOTE: SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 B) MULLIONS AS SHOWN ON PLANS FOR DOORS AND WINDOWS.
 NOTE: SPECIFY MULLION SIZE AND FASTENERS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) FRENCH DOORS AS SHOWN ON PLANS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS, WALL DETAILS AND TRUSS ANCHOR SCHEDULE.
 . PROVIDE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR ARCHITECT TO LIST ALL THE
 FLORIDA PRODUCT APPROVAL NUMBERS NEXT TO EACH SPECIFIED
 CONNECTOR. NOTE: FLORIDA PRODUCT APPROVAL FL474
 SPECIFIED ON THE TRUSS ANCHOR SCHEDULE NEEDS TO BE
 UPDATED. NEED THE CURRENT 2014 FBC APPROVAL.
  
 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: PLEASE PLACE REVIEW STAMP ON THE
 FRONT PAGE OF THE PRODUCT APPROVALS NOT ON THE BACK.
 THIS IS FOR PROPER SCANNING OF DOCUMENTS FOR RECORDS
 RETENTION PURPOSES.
  
 10- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE FOAM
 INSULATION SPECIFIED ON PLANS SHOWING COMPLIANCE WITH
 SEC. R316 FBC-RESIDENTIAL.
  
 11- ENERGY CALCULATIONS SUBMITTED. NOTE: THIS IS A
 CONTRIBUTING HISTORIC HOUSE. ENERGY CALCULATIONS ARE
 NOT REQUIRED, BUT IF CONTRACTOR WANTS TO SUBMITT THEM,
 THEN REVISE AS REQUIRED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION
 SHOWN ON PAGE 3 OF 4 TO MATCH PLANS SUBMITTED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABELS FOR DOORS AND WINDOWS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 ***PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  