Plan Review Notes For Permit 17020091 |
Permit Number |
17020091 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-07 17:17:28 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | 606.2.1 RETURN AIR SYSTEMS. | | SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR | | SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM | | (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF | | ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR | | CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND | | APPLIANCES. | | | | (1) MANUFACTURER SPECIFICATIONS OF THE RTU SPECIFIED ON | | THE PLANS ( ALLIED ZCA060S4BNX32330) HAVE A DESIGN | | CAPABILITY OF 2400 CFM MAXIMUM. AS PER 606.2.1 FBC | | MECHANICAL 2014 SMOKE DUCT DETECTORS ARE REQUIRED IN | | THE RETURN AIR. | | | | (2) PROVIDE APPROVED TIE DOWN DETAILS FOR ROOF CURB TO | | ROOF AND RTU TO CURB. | | | | FLORIDA ENERGY CODE FBC 2014 | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | |
|