Plan Review Notes For Permit 17020087 |
Permit Number |
17020087 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-06 09:21:26 | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE OF THE SUPPLY | | LINE FROM THE METER. THE LINE SHALL BE SIZED FOR THE | | TOTAL BTU LOAD ON THE SYSTEM. | | 2) SHOW THE PIPE SIZE OF THE UNDERGROUND PE LINE | | BETWEEN THE METER AND THE BRANCH FOR THE TTANKLESS | | WATER HEATER. | | 3) THE PLAN SHOWS A TOTAL BTU LOAD OF 299,000 BTU'S BUT | | I CALCULATE A TOTAL OF 359,000 BTU'S. CLARIFY. | | 4) THE FUTURE LINE FOR THE BBQ SHALL BE EQUIPPED WITH A | | VALVE, REGULATOR, NIPPLE AND CAP. | | 5) REMOVE THE SPECIFICATIONS FOR THE PIPE FROM THE | | PERMIT PACKAGE. THIS INFORMATION IS NOT REQUIRED AT | | THIS TIME. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|