Plan Review Notes For Permit 17020082 |
Permit Number |
17020082 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-05-02 15:19:11 | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | | | THE FOLLOWING SHALL BE SUBMITTED FOR REVIEW PRIOR TO | | THE FINAL ELECTRICAL INSPECTION. | | | | | | 1. FBC-RE 3601: SERVICE DISCONNECT SHALL BE SHOWN ON | | FLOORPLAN. IT SHALL BE MARKED AS REQUIRED. | | 2. FBC-RE 3609: THE INTERSYSTEM BONDING TERMINAL SHALL | | BE INCLUDED AND SHOW ON THE SERVICE DIAGRAM. | | 3. FBC-RE 3704: A SERVICE LOAD DIAGRAM SHALL BE | | PROVIDED AND A SERVICE DIAGRAM IS REQUIRED TO DETERMINE | | PROPER SIZING OF FEEDER CONDUCTORS. | | 4. FBC-RE 3705: THE LOCATION OF ALL ELECTRICAL PANELS | | SHALL BE MARKED ON THE FLOORPLANS. | | 5. FBC-RE 3901: TO COMPLY WITH THE OUTLET SPACING | | REQUIREMENTS OF THIS SECTION THERE IS AN OUTLET MISSING | | IN THE MASTER BEDROOM AND IN BEDROOM #2. | | | | |
|