Plan Review Notes
Plan Review Notes For Permit 17020082
Permit Number 17020082
Review Stop E
Sequence Number 3
Notes
Date Text
2017-05-02 15:19:11JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 THE FOLLOWING SHALL BE SUBMITTED FOR REVIEW PRIOR TO
 THE FINAL ELECTRICAL INSPECTION.
  
  
 1. FBC-RE 3601: SERVICE DISCONNECT SHALL BE SHOWN ON
 FLOORPLAN. IT SHALL BE MARKED AS REQUIRED.
 2. FBC-RE 3609: THE INTERSYSTEM BONDING TERMINAL SHALL
 BE INCLUDED AND SHOW ON THE SERVICE DIAGRAM.
 3. FBC-RE 3704: A SERVICE LOAD DIAGRAM SHALL BE
 PROVIDED AND A SERVICE DIAGRAM IS REQUIRED TO DETERMINE
 PROPER SIZING OF FEEDER CONDUCTORS.
 4. FBC-RE 3705: THE LOCATION OF ALL ELECTRICAL PANELS
 SHALL BE MARKED ON THE FLOORPLANS.
 5. FBC-RE 3901: TO COMPLY WITH THE OUTLET SPACING
 REQUIREMENTS OF THIS SECTION THERE IS AN OUTLET MISSING
 IN THE MASTER BEDROOM AND IN BEDROOM #2.
  
  