2017-02-06 13:21:29 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: |
| JOB ADDRESS: 306 MARLBORO PL |
| DESCRIPTION: COMPLETE INTERIOR REMODEL |
| MASTER PERMIT: 17020082 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| 1. ELECTRICAL SUB PERMIT REQUIRED. |
| 2. A SITE PLAN INDICATING THE LOCATION OF THE ELECTRIC |
| SERVICE UTILITY POLE AND ELECTRICAL METERS SHALL BE |
| SUBMITTED. |
| 3. FBC-RE 3601: SERVICE DISCONNECT SHALL BE SHOWN ON |
| FLOORPLAN. IT SHALL BE MARKED AS REQUIRED. |
| 4. FBC-RE 3602: SERVICE LOAD SHALL BE CALCULATED AS |
| INSTRUCTED AND SHOWN ON PLANS. |
| 5. FBC-RE 3609: THE INTERSYSTEM BONDING TERMINAL SHALL |
| BE INCLUDED AND SHOW ON THE SERVICE DIAGRAM. |
| 6. FBC-RE 3704: A SERVICE LOAD DIAGRAM SHALL BE |
| PROVIDED AND A SERVICE DIAGRAM IS REQUIRED TO DETERMINE |
| PROPER SIZING OF FEEDER CONDUCTORS. |
| 7. FBC-RE 3705: THE LOCATION OF ALL ELECTRICAL PANELS |
| SHALL BE MARKED ON THE FLOORPLANS. |
| 8. FBC-RE 3902: ARC-FAULT REQUIREMENTS EXTEND BEYOND |
| THE BEDROOMS AS MENTIONED ON PLANS. CORRECT |
| ACCORDINGLY. |
| 9. FBC-RE 3901: TO COMPLY WITH THE OUTLET SPACING |
| REQUIREMENTS OF THIS SECTION THERE IS AN OUTLET MISSING |
| IN THE MASTER BEDROOM AND IN BEDROOM #2. |
| 10. FBC-RE 3901: YOU SHALL MARK ON THE FLOORPLAN THE |
| LOCATION OF ALL HVAC EQUIPMENT AND SHOW THE REQUIRED |
| SERVICE OUTLETS AND ILLUMINATION. |
| 11. FBC-RE 3905: CEILING BOXES FOR THE SUPPORT OF |
| PADDLE FANS SHALL BE LISTED FOR THE PURPOSE AND MARKED |
| ACCORDINGLY. |
| 12. FBC-RE4001: THE GROUNDED CONDUCTOR SHALL BE |
| PROVIDED AT THE SWITCH AS REQUIRED. |
| 13. FBC-RE4002: TAMPER-RESISTANT RECEPTACLES SHALL BE |
| PROVIDED THROUGHOUT THE RESIDENCE. |
| 14. FBC-RE4003: RECESSED INCANDESCENT LUMINAIRES SHALL |
| HAVE THERMAL PROTECTION AND SHALL BE LISTED AS |
| THERMALLY PROTECTED. |
| 15. FBC-ER404.1 A MINIMUM OF 75% OF THE LAMPS IN |
| PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE |
| PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| ONLY HIGH EFFICIENCY LAMPS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |