2017-02-06 13:21:29ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 306 MARLBORO PL
 DESCRIPTION: COMPLETE INTERIOR REMODEL
 MASTER PERMIT: 17020082
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
 1. ELECTRICAL SUB PERMIT REQUIRED.
 2. A SITE PLAN INDICATING THE LOCATION OF THE ELECTRIC
 SERVICE UTILITY POLE AND ELECTRICAL METERS SHALL BE
 SUBMITTED.
 3. FBC-RE 3601: SERVICE DISCONNECT SHALL BE SHOWN ON
 FLOORPLAN. IT SHALL BE MARKED AS REQUIRED.
 4. FBC-RE 3602: SERVICE LOAD SHALL BE CALCULATED AS
 INSTRUCTED AND SHOWN ON PLANS.
 5. FBC-RE 3609: THE INTERSYSTEM BONDING TERMINAL SHALL
 BE INCLUDED AND SHOW ON THE SERVICE DIAGRAM.
 6. FBC-RE 3704: A SERVICE LOAD DIAGRAM SHALL BE
 PROVIDED AND A SERVICE DIAGRAM IS REQUIRED TO DETERMINE
 PROPER SIZING OF FEEDER CONDUCTORS.
 7. FBC-RE 3705: THE LOCATION OF ALL ELECTRICAL PANELS
 SHALL BE MARKED ON THE FLOORPLANS.
 8. FBC-RE 3902: ARC-FAULT REQUIREMENTS EXTEND BEYOND
 THE BEDROOMS AS MENTIONED ON PLANS. CORRECT
 ACCORDINGLY.
 9. FBC-RE 3901: TO COMPLY WITH THE OUTLET SPACING
 REQUIREMENTS OF THIS SECTION THERE IS AN OUTLET MISSING
 IN THE MASTER BEDROOM AND IN BEDROOM #2.
 10. FBC-RE 3901: YOU SHALL MARK ON THE FLOORPLAN THE
 LOCATION OF ALL HVAC EQUIPMENT AND SHOW THE REQUIRED
 SERVICE OUTLETS AND ILLUMINATION.
 11. FBC-RE 3905: CEILING BOXES FOR THE SUPPORT OF
 PADDLE FANS SHALL BE LISTED FOR THE PURPOSE AND MARKED
 ACCORDINGLY.
 12. FBC-RE4001: THE GROUNDED CONDUCTOR SHALL BE
 PROVIDED AT THE SWITCH AS REQUIRED.
 13. FBC-RE4002: TAMPER-RESISTANT RECEPTACLES SHALL BE
 PROVIDED THROUGHOUT THE RESIDENCE.
 14. FBC-RE4003: RECESSED INCANDESCENT LUMINAIRES SHALL
 HAVE THERMAL PROTECTION AND SHALL BE LISTED AS
 THERMALLY PROTECTED.
 15. FBC-ER404.1 A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved