2017-05-12 07:40:39 | ****PROVISO**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17020058 |
| ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2 |
| CONT: BRANCH CONSTRUCTION |
| TEL: 561-833-6206 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| SHEET 02-A SHOWS THE BREAKROOM DOOR # 06 DOES NOT |
| COMPLY WITH 2014 ACCESS. CODE 404.2.4 MANEUVERING |
| CLEARANCES. MINIMUM MANEUVERING CLEARANCES AT DOORS AND |
| GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES |
| SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE |
| REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE. |
| |
| 3RD REVIEW - APPLICANT HAS PROPOSED A RESOLUTION VIA |
| EMAIL. THIS PERMIT IS ISSUED WITH PROVISO - REVISE |
| SHEET 03-A AND OTHER AFFECTED SHEETS, BREAK ROOM 05 |
| DOOR TO COMPLY WITH FBC A 404.2.4 PRIOR TO FINAL |
| INSPECTION. |
| |
| |