Plan Review Notes
Plan Review Notes For Permit 17020058
Permit Number 17020058
Review Stop P
Sequence Number 1
Notes
Date Text
2017-02-15 15:54:591ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE TOILET PAPER DISPENSER SHOW 0'-8' OFF THE FRONT
 OF TOILET IT SHALL BE 7 "- 9" MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER 604.7
  
 2. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 3. SHOW CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL. PER FBC ACC 604.3.1
  
 4. SHOW CLEAR FLOOR SPACE FOR LAV 30" X 48". PER FBC
 ACC 606.2
  
 5. SHT P-2 THE DETAIL FOR THE WATER HEATER SHOWS T+P
 DRAIN AND PAN DRAIN TERMINATING ABOVE A MOP SINK THERE
 IS NO MOP SINK SHOWN ON PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  