2017-02-06 12:55:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020058
 2/6/17
  
 1) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR
 SYSTEM OF THE NEW HEAT PUMP- SECTION 606.2.1.
  
 2) PROVIDE AN AUTOMATIC SHUTOFF DAMPER FOR THE O/A
 INTAKE DUCT- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  