Plan Review Notes For Permit 17020058 |
Permit Number |
17020058 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-06 12:55:06 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17020058 | | 2/6/17 | | | | 1) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR | | SYSTEM OF THE NEW HEAT PUMP- SECTION 606.2.1. | | | | 2) PROVIDE AN AUTOMATIC SHUTOFF DAMPER FOR THE O/A | | INTAKE DUCT- SECTION C403.2.4.4 FBC-14 ENERGY | | CONSERVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|