Plan Review Notes
Plan Review Notes For Permit 17020058
Permit Number 17020058
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-02-09 10:12:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET O2 A - THE RESTROOM DOOR OPENS INTO THE EXIT
 CORRIDOR.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET O2 A - THERE IS A PIECE OF FURNITURE LOCATED
 IN FRONT OF A SET OF DOUBLE DOORS THAT ARE INDICATED AS
 OPEN. THOUGH THE OTHER SET OF DOORS ARE INDICATED AS
 THE EXIT DOORS, PLEASE INDICATE IF THESE WILL BE LOCKED
 AND CLEARLY MARKED AS NOT EXIT DOORS.
  
 PLEASE REVIEW, CLARIFY AAAAAND CORRECT.
  
  
  
  
 3) SHEET O3 A - THERE IS AN EXIT SIGN IN THE CORRIDOR
 LEADING INTO TREATMENT ROOM 7; HOWEVER, THERE IS NO
 EXIT SIGN INDICATED ON SHEET E 1.
  
 HOWEVER, PER NFPA 101, CHAPTER 7, MEANS OF EGRESS -
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS
 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR
 SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO
 LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS
 PERMITTED FOR THE OCCUPANCY BY CHAPTER18, 19, 22, OR
 23.
  
 TREATMENT ROOM 7 DOOR CAN NOT BE MARKED AS AN EXIT.
  
 PLEASE CORRECT SHEET O3 A AND ENSURE AN EXIT SIGN IS
 NOT PALCED ABOVE THAT DOOR.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  