2017-02-03 16:13:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020058
 ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2
 CONT: BRANCH CONSTRUCTION
 TEL: 561-833-6206
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 03/ 2017
 ACTION: DENIED
  
 1) SHEET 01-A THE COVERSHEET LIST THIS BUILDING AS A
 BUILDING TYPE III-B. PLEASE NOTE THIS IS A 20 STORY
 HIGH RISE BUILDING. PLEASE CORRECT TO A MINIMUM
 BUILDING TYPE I-A CONSTRUCTION, SEE 2014 FBC-B TABLE
 503.
  
 2) SHEET 01-A THE COVERSHEET ALSO LIST THE OCCUPANCY
 TYPE AS A-2 ASSEMBLY AND B OCCUPANCY. THE OCCUPANCY
 TYPE PER SECTION 304.1 IS A B/ BUSINESS OCCUPANCY.
  
 3) SHEET 01-A THE COVERSHEET ALSO LIST THE BUILDING
 FIRE PROTECTION AS UNPROTECTED / SPRINKLERED NEW
 SYSTEM. PLEASE PROVIDE THE MEANING OF UNPROTECTED. IN
 THE 2014 FBC-B TABLE 601 THE BUILDING ELEMENT TABLE
 REQUIRES ALL STRUCTURAL ELEMENTS TO BE FIRE RATED IN
 HOURS.
  
 4) SHEET 01-A THE COVERSHEET ALSO LIST THE OCCUPANT
 LOAD AS 10 IN THE UPPER RIGHT HAND CORNER OF THE SHEET,
 BUT IN THE LOWER RIGHT CORNER OF THE SHEET THE HEADING
 OF BUILDING DATA AND A/C CALCULATIONS BOTH INDICATE THE
 SQUARE FOOTAGE OF THE TENANT SPACE AS 1,182 SQUARE
 FEET. 1,182/100= 12 OCCUPANTS TABLE 1004.1.2.
  
 5) SHEET 02-A SHOWS THE BREAKROOM DOOR # 06 DOES NOT
 COMPLY WITH 2014 ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. MINIMUM MANEUVERING CLEARANCES AT DOORS AND
 GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES
 SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE
 REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 6) SHEET 02/A DOES NOT SHOW COMPLIANCE FOR THE BREAK
 ROOM SINK, COMPLIANCE WITH 2014 ACCESS. CODE
 606.3 HEIGHT.
 606.2 CLEAR FLOOR SPACE.
 606.4 FAUCETS.
 606.5 EXPOSED PIPES AND SURFACES.
  
 7) SHEET 02/A THE RECEPTION DESK DOES NOT INDICATE
 COMPLIANCE WITH 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE
 TOPS WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676