Date |
Text |
2017-03-08 18:03:25 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY MECHANICAL |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING |
| EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS |
| CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER |
| APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. |
| PROVIDE EQUIPMENT SIZING CALCULATIONS. |
| |
| 2) SHOW COMPLIANCE WITH FBC-R - M 1602.4 FOR BALANCED |
| RETURN AIR. |
| |
| 3) FBC-R - M1305.1.3 AIR-HANDLING UNITS. |
| 2014 FBC ENERGY CONSERVATION R403.2.4 |
| AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE |
| FOLLOWING CONDITIONS ARE MET: |
| 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE |
| UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| PROPERLY. |
| 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| REPLACE THE AIR HANDLER. |
| 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST |
| PARAGRAPH IN BOLD: |
| |
| NOTICE TO HOMEOWNER |
| |
| A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR |
| HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT |
| AND ECONOMIC OPERATION OF THE AIR CONDITIONING SYSTEM, |
| YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. |
| YOUR AIR CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR |
| BOTH OF THE FOLLOWING: |
| |
| 1)A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION |
| DRAIN IS NOT WORKING PROPERLY OR |
| |
| 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE |
| CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL |
| DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF |
| SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER |
| WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF |
| PEAK OPERATION. |
| |
| 4) SHOW THE RETURN LOCATION AND SIZE ON THE PLANS. FBC |
| 107.2.1 |
| |
| 5) SHOW THE LOCATION AND SIZE OF THE ATTIC ACCESS |
| OPENING ON THE PLANS. FBCR-M1305.1.3 |
| |
| 6) SHOW THE CLOTHES DRYER EXHAUST DUCT AND THE BATHROOM |
| EXHAUST DUCTS ON THE PLANS. FBCR - M1502, M1507 & |
| FBC-R303.3 |
| |
| |