2018-02-15 12:17:41 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ESTIMATED AIC CALCULATIONS ARE NOT ACCEPTABLE. |
| PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. WE |
| WILL ACCEPT THIS AS A DEFERRED SUBMITTAL WITH THE |
| UNDERSTANDING THAT THIS WILL BE PROVIDED PRIOR TO |
| INSPECTION SO THE INSPECTOR CAN VERIFY EQUIPMENT IS |
| PROPERLY SIZED AND LABELED. NEC 110.9, 110.10 |
| 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS FOR THE MAIN SERVICE. IF FOR FUTURE TENANTS, |
| PROVIDE BASIS FOR SIZE OF SERVICE BASED ON SQUARE |
| FOOTAGE DEMANDS EXPECTED. NEC 220, 215.2 |
| 3. IS THE EXISTING SERVICE WIRE THE SAME AS PROPOSED IN |
| THE NEW SERVICE MAST BEING ADDED? PROVIDE |
| CLARIFICATION. NEC 310.10(H)(2) |
| 4. CIRCUIT HP2-4 IS SHOWN IN PANEL SCHEDULE AS THE EWC, |
| BUT IT IS SHOWN ON PLAN AS LIGHTING CIRCUIT. EWC MUST |
| HAVE A DEDICATED CIRCUIT THAT IS GFCI PROTECTED. |
| PROVIDE CORRECTION. NEC 422.52 |
| 5. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED |
| FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| CORRECTION. NEC 700.12(F) |
| |
| ALSO, THERE ARE PREVIOUS COMMENTS NOT ADDRESSED: |
| FURTHER COMMENTS IN PARENTHESES. |
| |
| INITIAL ELECTRICAL PLAN REVIEW |
| |
| 1. PLEASE NOTE THAT A NEW ELEVATOR IS INDICATED ON |
| APPLICATION, SHOW ALL NEW LOADS FOR ELEVATOR REFLECTED |
| ON PANEL SCHEDULE ASSIGNED. COMPLY WITH ALL NEC 620.24 |
| BRANCH CIRCUIT HOIST WAY PIT, SUMP, LIGHTING, |
| RECEPTACLE ETC. 620.51 DISCONNECTING MEANS AND CONTROLS |
| (A-D) AND PART8- CONTROL SPACES ETC. (PROVIDE NOTE THAT |
| ELEVATOR WILL BE UNDER SEPARATE PERMIT.) |
| 2. (ADDRESSED, BUT NEEDS CORRECTIONS. SEE COMMENT 3 |
| ABOVE.) |
| 3. PROVIDE A NOTE THAT NO ELECTRICAL THAT IS NOT PART |
| OF THE STAIRWELL CAN PASS THRU THE AREA. FBC 107.3.5 |
| (DID NOT SEE NOTE ON PLAN.) |
| 4. ADDRESSED. |
| 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| VERBIAGE IN CODE. (NEED TO QUOTE BOTH CODE SECTIONS ON |
| PLAN FOR DIFFERENT TYPE OF LABELS REQUIRED.) |
| 6. SHOW PER FBC EC 405- THE AUTOMATIC MEANS OF LIGHTING |
| CONTROLS PER ENERGY CODE AND COMPLIANCE WITH LIGHTING |
| DENSITIES. (DID NOT COMPLY) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |