Plan Review Notes For Permit 17020029 |
Permit Number |
17020029 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-10 15:16:03 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE NOTE THAT A NEW ELEVATOR IS INDICATED ON | | APPLICATION, SHOW ALL NEW LOADS FOR ELEVATOR REFLECTED | | ON PANEL SCHEDULE ASSIGNED. COMPLY WITH ALL NEC 620.24 | | BRANCH CIRCUIT HOIST WAY PIT, SUMP, LIGHTING, | | RECEPTACLE ETC. 620.51 DISCONNECTING MEANS AND CONTROLS | | (A-D) AND PART8- CONTROL SPACES ETC. | | 2. PROVIDE EXISTING ONE-LINE DIAGRAM FOR THE ELECTRICAL | | SERVICE. FBC 107.3.5 | | 3. PROVIDE A NOTE THAT NO ELECTRICAL THAT IS NOT PART | | OF THE STAIRWELL CAN PASS THRU THE AREA. FBC 107.3.5 | | 4. ADDRESS FIRE AND BUILDING COMMENTS IMPACTING THE | | ELECTRICAL SCOPE OF WORK. | | 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC | | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE | | VERBIAGE IN CODE. | | 6. SHOW PER FBC EC 405- THE AUTOMATIC MEANS OF LIGHTING | | CONTROLS PER ENERGY CODE AND COMPLIANCE WITH LIGHTING | | DENSITIES. | | 7. COMMENTS MAY FOLLOW UPON RESUBMITTAL. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|