2017-02-10 15:16:03INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE NOTE THAT A NEW ELEVATOR IS INDICATED ON
 APPLICATION, SHOW ALL NEW LOADS FOR ELEVATOR REFLECTED
 ON PANEL SCHEDULE ASSIGNED. COMPLY WITH ALL NEC 620.24
 BRANCH CIRCUIT HOIST WAY PIT, SUMP, LIGHTING,
 RECEPTACLE ETC. 620.51 DISCONNECTING MEANS AND CONTROLS
 (A-D) AND PART8- CONTROL SPACES ETC.
 2. PROVIDE EXISTING ONE-LINE DIAGRAM FOR THE ELECTRICAL
 SERVICE. FBC 107.3.5
 3. PROVIDE A NOTE THAT NO ELECTRICAL THAT IS NOT PART
 OF THE STAIRWELL CAN PASS THRU THE AREA. FBC 107.3.5
 4. ADDRESS FIRE AND BUILDING COMMENTS IMPACTING THE
 ELECTRICAL SCOPE OF WORK.
 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 6. SHOW PER FBC EC 405- THE AUTOMATIC MEANS OF LIGHTING
 CONTROLS PER ENERGY CODE AND COMPLIANCE WITH LIGHTING
 DENSITIES.
 7. COMMENTS MAY FOLLOW UPON RESUBMITTAL.
  