2017-02-09 10:31:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020029
 ADD: 325 CLEMATIS ST. 1ST & 2ND FLOOR ALTERATIONS.
 CONT: MAC ENTERPRISES
 TEL: 561-236-3627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 NOTE: 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: TUES. FEB. 07/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET T.1:
 1A) UNDER THE 2014 FL. EXISTING BUILDING CODE THE
 DESIGNER OF RECORD HAS DECLARED A LEVEL III ALTERATION
 FOR COMPLIANCE METHOD. PLEASE NOTE THERE ARE (2) WORK
 AREAS, ONE EACH FLOOR AND (2) OCCUPANCIES.
 THE 2ND FLOOR IS TO BE CONSIDERED A LEVEL III
 ALTERATION WHEREAS THE 1ST FLOOR IS A CHANGE OF
 OCCUPANCY FROM MERCANTILE TO A FUTURE A2 RESTAURANT.
 THE FUTURE A2 RESTAURANT WILL BE CONSIDERED A CHANGE OF
 OCCUPANCY AND WILL NEED TO COMPLY WITH SECTION 506.2
 EXIST. BUILDING CODE. CHANGES OF OCCUPANCY SHALL COMPLY
 WITH THE PROVISIONS OF CHAPTER 10.
 EXIST. BUILDING CODE 1001.3.1 PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN
 EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 1012 SHALL APPLY. PLEASE
 CORRECT PLANS ACCORDINGLY. THANK YOU.
  
 1B) THE COVERSHEET INDICATES A TYPE VB BUILDING TO BE
 FIRE SPRINKLERED.
 THE EXIST. BUILD. CODE 1012.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
 2014 FBC-B 903.2.1.2 GROUP A-2. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED FOR GROUP A-2 OCCUPANCIES
 WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2);
 THE TOTAL AREA OF THE 1ST FLOOR TENANT 6,068
 SQUARE FEET, SEE 2012 IBC-B DEFINITION OF BUILDING AREA
 FIGURE 202.1(7). THE HORIZONTAL PROJECTION
 OF THE FLOOR ABOVE DEFINES AREA THAT IS INCLUDED AS
 PART OF THE BUILDING AREA.
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE;
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS. BUILDING.
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 1C) PLEASE NOTE THE 2ND FLOOR TOTAL SQUARE FOOT AREA IS
 6,517 SQUARE FEET IN AREA, THE SAME WOULD BE FOR THE
 1ST FLOOR. THE AREA ALLOWED FOR AN A2 OCCUPANCY1ST
 FLOOR FOR A VB BUILDING IS 6,000 SQUARE FEET. PLEASE
 UPDATE THE PLANS FOR THE REQUIRED AREA MODIFICATION
 INCREASE FOR EITHER 506.2 FRONTAGE OR 506.3 AUTOMATIC
 SPRINKLER SYSTEM INCREASE.
 SEE EQUATION 5-1.
  
 1D) THE LIFE SAFETY PLAN SHOW AN EXISTING MECHANICAL
 ROOM (104) THAT APPEARS TO BE A 2 STORY MECHANICAL
 PLATFORM. PLEASE PROVIDE A NORTH SOUTH CUT SECTION
 THROUGH THE ROOM TO SEE THE ELEVATION OF THE 2ND FLOOR
 LEVEL IN RELATION TO ELEVATION OF THE 1ST FLOOR. IS
 THIS ONE MECHANICAL UNIT THAT WILL BE FOR BOTH FLOORS
 AND TENANTS? 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 1E) THE COVERSHEET T.1 DOES NOT INDICATE IF THE 2
 FLOORS ARE GOING TO BE UNDER THE CONTROL OF A SINGLE
 TENANT OR IF THERE ARE GOING TO BE (2) SEPARATE TENANTS
 THAT WILL SHARE BACK OF HOUSE RESTROOMS AND OTHER
 COMMON ELEMENTS? NO RESTROOMS ARE SHOWN ON EITHER
 FLOOR. 2014 FBC-B 2902.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED FOR THE TYPE OF
 OCCUPANCY AND IN THE MINIMUM NUMBER SHOWN IN TABLE
 2902.1. TYPES OF OCCUPANCIES NOT SHOWN IN TABLE 2902.1
 SHALL BE CONSIDERED INDIVIDUALLY BY THE BUILDING
 OFFICIAL. THE NUMBER OF OCCUPANTS SHALL BE DETERMINED
 BY THIS CODE. OCCUPANCY CLASSIFICATION SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTER 3.
  
 1F) LIFE SAFETY SHEET SHOWS THE A2 FIRST FLOOR
 OCCUPANCY OF 151 OCCUPANTS AND THE 2ND FLOOR OCCUPANCY
 LOAD OF 61 FOR BUSINESS OCCUPANCY. THE 2ND FLOOR AREA
 GROSS SEE DEFINITION. AREA, BUILDING. THE AREA INCLUDED
 WITHIN SURROUNDING EXTERIOR WALLS (OR EXTERIOR WALLS
 AND FIRE WALLS) EXCLUSIVE OF VENT SHAFTS AND COURTS.
 AREAS OF THE BUILDING NOT PROVIDED WITH SURROUNDING
 WALLS SHALL BE INCLUDED IN THE BUILDING AREA IF SUCH
 AREAS ARE INCLUDED WITHIN THE HORIZONTAL PROJECTION OF
 THE ROOF OR FLOOR ABOVE.
 THE 2ND FLOOR IS APPROXIMATELY 138X48 SQ. FT.= 6,624
 SQ. FT./ 100= 67 OCCUPANTS.
 THE 1ST FLOOR ASSEMBLY USAGE CURRENTLY IS SHOWN AS A
 SHELL WHICH WILL MAKE THE OCCUPANT LOAD EXTREMELY HIGH,
 NO RESTROOMS NOR KITCHEN NOR STORAGE HAS BEEN SHOWN ON
 THIS PLAN.
 6068 SQ. FT/ 5= 1,214 OCCUPANTS (STANDING SPACE)
 6068 SQ. FT./ 7= 867 OCCUPANTS (CONCENTRATED CHAIRS
 ONLY NOT FIXED)
 6068 SQ. FT./15= 405 OCCUPANT LOAD (UNCONCENTRATED,
 TABLES & CHAIRS)
 WITH THE CURRENT LAYOUT THE (2) EXIT DOORS SHOWN ON THE
 PLANS WILL NOT ALLOW FOR EXITING.
  
 1G) PLEASE PROVIDE THE OVERALL DIMENSION OF THE EXIT
 DOORS. THE L.S. SHEET INDICATES BOTH THE FRONT AND REAR
 DOORS ARE A WIDTH OF 35 INCHES AND EXIT CAPACITY OF 175
 OCCUPANTS. PLEASE IDENTIFY THE OVERALL DIMENSION OF THE
 DOOR AND THE CLEAR OPENING OF THE DOOR. 1008.1.1 SIZE
 OF DOOR. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES. IT WOULD APPEAR
 THESE ARE 3 FOOT WIDE DOORS WITH A 34 INCH CLEAR
 OPENING ONLY ALLOWING 340 OCCUPANTS THROUGH THE DOOR
 OPENING.
  
 1H) PLEASE PROVIDE THE STAIRWAY WIDTH FOR BOTH THE
 FRONT STAIR (NEW) AND REAR STAIR (EXISTING) TO
 DETERMINE THE MEANS OF EGRESS CAPACITY FOR THE STAIR.
 SHOW COMPLIANCE WITH 2014 FBC-B 1005.3.1.
  
 1I) ) THE COVERSHEET T.1 NOR THE LS.1 INDICATE
 COMPLIANCE WITH HORIZONTAL OCCUPANCY SEPARATION 2014
 FBC-B 707.3.10 & TABLE 707.3.10.
  
 2A) THE REAR STAIRS, IT IS HARD TO TELL IF THIS STAIR
 IS BEING DESIGNED AS AN ENCLOSED STAIR OR IF THE
 DESIGNER IS TRYING TO VIEW THIS STAIR AS AN EXIT ACCESS
 STAIRWELL (FBC-B 1009.3 & 1016.3.1) OR AS A RATED EXIT
 STAIR (1022.2). IF DESIGNED AS AN EXIT ACCESS STAIR
 TRAVEL DISTANCE NEEDS TO BE IN CONFORMANCE WITH FBC-B
 1016.3.
  
 2B) THE REAR STAIR WALL RATING IS CLEARLY SHOWN ON THE
 2ND FLOOR AS DARKER AROUND THE 2ND FLOOR CORRIDOR AND
 LIGHTER IN THE SOUTH WALL OF THE STAIRWELL. ON THE 1ST
 FLOOR THERE APPEARS TO BE NO RATING THAT WOULD SEPARATE
 THE STAIRWELL FROM THE 1ST FLOOR TENANT. FBC-B 1022.2).
  
 2C) 1ST FLOOR BACK OF HOUSE, IF THE REAR STAIR IS TO BE
 CONSIDERED A EXIT STAIR (1 HOUR RATED) THEN 3 THINGS
 NEED TO HAPPEN:
  
 2C)(1) THE REAR EXIT WILL LEAD INTO A EXIT PASSAGE WAY
 AND TO THE EXIT DOOR. BETWEEN THE EXIT STAIR WELL AND
 EXIT PASSAGE WAY SECTION FBC-B 1022.3.1 EXTENSION. THE
 FIRE-RESISTANCE RATING SHALL BE AT LEAST EQUAL TO THAT
 REQUIRED FOR THE INTERIOR EXIT STAIRWAY AND RAMP. A
 FIRE RATED DOOR ASSEMBLY COMPLYING WITH SECTION 716.5
 SHALL BE INSTALLED IN THE FIRE BARRIER TO PROVIDE A
 MEANS OF EGRESS FROM THE INTERIOR EXIT STAIRWAY AND
 RAMP TO THE EXIT PASSAGEWAY. OPENINGS IN THE FIRE
 BARRIER OTHER THAN THE FIRE DOOR ASSEMBLY ARE
 PROHIBITED. PENETRATIONS OF THE FIRE BARRIER ARE
 PROHIBITED.
  
 2C)(2) THE EXIT PASSAGEWAY WILL NEED TO BE SEPARATED
 FROM THE ELEVATOR AND REMOVAL OF THE HOUSE PANELS.
 1023.5 OPENINGS AND PENETRATIONS.
 EXIT PASSAGEWAY OPENING PROTECTIVES SHALL BE IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 716. EXCEPT
 AS PERMITTED IN SECTION 402.8.7, OPENINGS IN EXIT
 PASSAGEWAYS OTHER THAN EXTERIOR OPENINGS SHALL BE
 LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO THE EXIT
 PASSAGEWAY FROM NORMALLY OCCUPIED SPACES AND FOR EGRESS
 FROM THE EXIT PASSAGEWAY. WHERE AN INTERIOR EXIT
 STAIRWAY OR RAMP IS EXTENDED TO AN EXIT DISCHARGE OR A
 PUBLIC WAY BY AN EXIT PASSAGEWAY, THE EXIT PASSAGEWAY
 SHALL ALSO COMPLY WITH SECTION 1022.3.1. ELEVATORS
 SHALL NOT OPEN INTO AN EXIT PASSAGEWAY.
 1023.6 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT
 PASSAGEWAY AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2C)(3)(A) THE 3RD ISSUE IS THERE IS A COLUMN LOCATED IN
 THE EXIT PASSAGE WAY OR EXIT ACCESS STAIRWELL AND
 MECHANICAL PLATFORM/ MEZZANINE ABOVE. PLEASE PROVIDE
 THE CLEAR HEIGHT FROM THE BOTTOM OF THE MEZZANINE LEVEL
 TO THE TOP OF THE 1ST FLOOR FINISH FLOOR. SEE FBC-B
 1003.2 & 1003.3.1 HEADROOM.
  
 2C)(3)(B) THE 3RD ISSUE IS THERE IS A COLUMN LOCATED IN
 THE EXIT PASSAGE WAY OR EXIT ACCESS STAIRWELL AND
 MEZZANINE ABOVE. PLEASE PROVIDE THE CLEAR HEIGHT FROM
 THE BOTTOM OF THE MEZZANINE LEVEL TO THE TOP OF THE 1ST
 FLOOR FINISH FLOOR. SEE FBC-B 1003.2 & 1003.3.1
 HEADROOM.
  
 3) THE STRUCTURAL SHEETS SHOW A SCOPE OF WORK THAT WILL
 REQUIRE A RESIDENT INSPECTOR ON THIS PROJECT. 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE
 INCH
 4. FOR HELICAL PILE
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 3A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS WERE E-MAILED TO: [email protected]
 TUES. FEB. 07/2017 03:24 PM
  
 3B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 3C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 3E) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 4) TO DATE NO SOILS REPORTS WERE SUBMITTED FOR THIS
 PROJECT. SHEET S-4.0 NOTE 4 INDICATES THE GEOTECHNICAL
 ENGINEER SHALL INSPECT AND REQUIRE TESTING AS NECESSARY
 TO ASSURE THAT THE FOUNDATION PILES ARE INSTALLED IN
 ACCORDANCE WITH THEIR SPECIFICATIONS AND REPORT ANY
 DEVIATIONS TO THE ENGINEER.
 1804.1 EXCAVATION NEAR FOUNDATIONS. EXCAVATION FOR ANY
 PURPOSE SHALL NOT REMOVE LATERAL SUPPORT FROM ANY
 FOUNDATION WITHOUT FIRST UNDERPINNING OR PROTECTING THE
 FOUNDATION AGAINST SETTLEMENT OR LATERAL TRANSLATION.
  
 5) ) SHEET S-1.0 IN THE SOUTHEAST CORNER OF THE
 BUILDING THERE IS A NOTE PRE-ENGINEERED STAIRS BY
 OTHERS, THERE IS NO DESIGN CRITERIA FOR LIVE LOADS
 (FBC-B TABLE 1604.5) TO BE CARRIED NOR DOES THE NOTE
 INDICATE CLOSED RISERS FBC-B 1009.7.5.
  
 6) NONE OF THE STRUCTURAL SHEETS, NEITHER ARCHITECTURAL
 SHEETS NOR THE MECHANICAL SHEETS SHOW ROOF TOP ACCESS
 FOR THE MECHANICAL EQUIPMENT. PLEASE SHOW COMPLIANCE
 WITH:
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES. WHERE EQUIPMENT AND APPLIANCES
 REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 MM),
 SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED
 MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM
 GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES?
 LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES (762
 MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE GREATER
 THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS
  
 7A) ROOF TOP MECHANICAL EQUIPMENT MAY REQUIRE SCREENING
 AS A ZONING REQUIREMENT. ? 1509.6 MECHANICAL EQUIPMENT
 SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 7B) IF MECHANICAL SCREENS ARE REQUIRED THEN THE
 STRUCTURAL MEMBERS WILL BE REQUIRED TO BE ATTACHED TO
 THE ROOF FRAMING TO BE PART OF THE MWFRS (MAIN WIND
 FORCE RESISTING SYSTEM).
  
 8) ROOF TOP MECHANICAL EQUIPMENT WILL NEED TO SHOW
 COMPLIANCE WITH: 2014 FBC- ? M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 9) NOTE DEPENDING ON THE 2ND FLOOR EXITING IS TO BE
 DEFINED IF IT IS A EXIT ACCESS STAIR OR AS A VERTICAL
 EXIT AND EXIT PASSAGE WAY FBC-B 1022.5 PENETRATIONS
 ONLY ALLOWS IN EXITS EQUIPMENT, DUCTWORK NECESSARY FOR
 INDEPENDENT VENTILATION OR PRESSURIZATION.
  
 10) SHEET S-4.0 PROVIDES THE WIND DESIGN CRITERIA, THE
 MEAN ROOF HEIGHT IS NOT PROVIDED NEITHER IS THE
 PRESSURES FOR COMPONENTS AND CLADDING.
 2014 FBC-B TABLE 1604.5 RISK CATEGORY PLEASE NOTE
 BUILDINGS WHOSE PRIMARY OCCUPANCY IS PUBLIC ASSEMBLY
 WITH AN OCCUPANT LOAD OF GREATER THAN 300 THE RISK
 CATEGORY WOULD BE III NOT A II. THEN THE WIND VULT WIND
 DESIGN WOULD BE 180 VULT PER FIGURE 1609B.
 FBC-B 2014 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR
 HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 FBC-B 2014 FBC-B 1603.1.4 WIND DESIGN DATA. (5) VASD
 POSITIVE AND NEGATIVE PRESSURES.
  
 11) PRODUCT APPROVALS: COMPONENTS & CLADDING. 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 12) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) EITHER THE CONTRACTOR OR THE DESIGNER OF RECORD MAY
 REQUEST THE PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING TO BE DEFERRED. 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) CHANGE OF OCCUPANCY ASSEMBLY: IMPACT FEES BEFORE A
 PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 15) THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  