2017-03-31 15:00:53 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- REVISED ENERGY CALCULATIONS FORM R405-2014 |
| SUBMITTED: |
| A) OWNER DIDN'T CERTIFIED CODE COMPLIANCE AT THE BOTTOM |
| OF FORM AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| NOTE: IT WAS DONE ON THE ORIGINAL SUBMITTAL BUT NOT ON |
| THE REVISED ONE. PERMIT CAN NOT BE ISSUED WITHOUT THE |
| OWNER'S CERTIFICATION. |
| |
| B) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED |
| BY SEC. R405.4.3 FBC-ENERGY CONSERVATION. |
| RESPONSE: REPEAT COMMENT. EPL DISPLAY CARD WAS NOT |
| COMPLETED BY THE BUILDER. BUILDER NEEDS TO FILL THIS |
| FORM. SEE EPL DISPLAY CARD IN THE ENERGY CALCULATIONS |
| PACKAGE. |
| |
| C) INFORMATION ON TOP OF FORM SUBMITTED IS INCORRECT. |
| PROVIDE THE CORRECT BUILDER'S NAME. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| RESPONSE: BUILDER'S NAME IS INCORRECT AGAIN. |
| |
| 2- VALUATION DECLARED IN THE PERMIT APPLICATION DIDN'T |
| INCLUDE THE DESIGN PROFESSIONAL FEES AS REQUIRED BY |
| SEC. 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED TO |
| INCLUDE THE DESIGN FEES OF ALL DESIGN PROFESSIONALS. |
| VALUATION WAS ROUNDED TO $50,000 +/- TO INCLUDE THE |
| DESIGN FEES OF ALL ENGINEERS INVOLVED IN THIS PROJECT. |
| THE PERMIT FEE BALANCE IS $1235.88. |
| |