Plan Review Notes
Plan Review Notes For Permit 17011187
Permit Number 17011187
Review Stop G
Sequence Number 1
Notes
Date Text
2017-02-01 06:50:531) THERE IS AN EXISTING GAS SYSTEM AT THIS ADDRESS THAT
 WAS SIZED AS A LESS THAN 2 PSI SYSTEM AND THE SUBMITTED
 PLAN NOTES IT WILL NOW BE A 2 PSI SYTEM. REGULATORS
 WILL BE REQUIRED ON EACH EXISTING APPLIANCE. SUBMIT
 MANUF. SPECIFICATIONS FOR THE STEP DOWN REGULATORS THAT
 WILL BE INSTALLED.
 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
 3) SHOW THE SIZE OF THE GAS SUPPLY LINE ON THE OUTLET
 AT THE GAS METER. THE SUPPLY LINE SHALL BE BASED ON THE
 TYPE OF MATERIAL, THE DISTANCE TO THE FURTHEST OUTLET
 AND THE TOTAL BTU LOAD ON THE SYSTEM.
 4) SHOW THE TYPE OF PIPE MATERIAL AND THE SIZE OF THE
 PIPE THAT IS DOWNSTREAM OF THE 2 PSI REGULATOR FOR THE
 POOL HEATER.
 5) SUBMIT 2 COPIES OF THE MANUFACTURERR'S
 SPECIFICATIONS FOR THE POOL HEATER. THE POOL HEATER
 SHALL BE LISTED AND LABELED AND COMPLY WITH THE 2014
 FBC-ENERGY CODE.
 6) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  