Plan Review Notes For Permit 17011186 |
Permit Number |
17011186 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-09 17:23:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) HOW WILL THE LIGHTING BE INSTALLED, THE SEPARATION | | DISTANCE AND LUMENS. | | | | ELECTRICAL DRAWINGS AMY NEED TO BE SUBMITTED. | | | | | | | | 2) PLEASE PROVIDE A NOTE INDICATING THE SIDE ALONG | | ROSEMARY DOES NOT HAVE SIDES, FENCING, OR MATERIAL THAT | | WOULD LIMIT FREE EGRESS. | | | | | | | | 3) PROVIDE DETAILS IF THIS PROPOSED STRUCTURE AFFECTS | | THE EGRESS OF THE ALF BUILDING ALLEY EXIT. | | | | | | | | 4) BUILDING DEPARTMENT COMMENTS NEED TO BE ADDRESSED. | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|