Plan Review Notes For Permit 17011047 |
Permit Number |
17011047 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-02 09:10:59 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY ELECTRICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBCR-E3602.2 - SUBMIT ELECTRICAL LOAD CALCULATIONS | | FOR THE DWELLING TO SHOW THAT THE EXISTING SERVICE IS | | ADEQUATE FOR THE POOL HEATER AND OTHER POOL EQUIPMENT. | | | | 2) FBCR-E4203.1.2 - PROVIDE AT LEAST ONE 125-VOLT, 15- | | OR 20-AMPERE RECEPTACLE A MINIMUM OF 6 FEET FROM BUT | | NOT MORE THAN 20 FEET FROM THE INSIDE WALL OF THE POOL. | | | | |
|