Plan Review Notes For Permit 17011033 |
Permit Number |
17011033 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-01-27 14:41:35 | UPDATE ARMOVER DETAIL: 9.2.3.5.2 UNSUPPORTED ARMOVER | | LENGTH WITH MAXIMUM PRESSURE EXCEEDING 100 PSI | | SUPPLYING SPRINKLERS IN A PENDENT POSITION BELOW THE | | CEILING. | | WHERE THE MAXIMUM STATIC OR FLOWING PRESSURE, WHICHEVER | | IS GREATER AT THE SPRINKLER, APPLIED OTHER THAN THROUGH | | THE FIRE DEPARTMENT CONNECTION, EXCEEDS 100 PSI AND A | | BRANCH LINE ABOVE A CEILING SUPPLIES SPRINKLERS IN A | | PENDENT POSITION BELOW THE CEILING, THE CUMULATIVE | | HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER TO A | | SPRINKLER OR SPRINKLER DROP SHALL NOT EXCEED 12-INCHES | | FOR STEEL PIPE. | | | | |
|