2017-03-17 06:16:42 | 1) THE SCOPE OF WORK LISTED IN THE DOCUMENT FROM ALL |
| FLORIDA STRUCTURES DATED 1/19/2017 INDICATES THAT BOTH |
| OF THESE TOILET ROOMS ARE EXISTING HANDICAPPED (ADA) |
| TOILET ROOMS BUT THE REVISED PLANS FROM GENTRY |
| ENGINEERING NOTES THAT ONLY ONE TOILET ROOM IS |
| HANDICAPPED ACCESSIBLE. AT THIS POINT I HAVE NO IDEA |
| WHICH IS WHICH DUE TO THE CONFLICTING INFORMATION THAT |
| HAS BEEN SUBMITTED AND VAGUE INFORMATION ON THE PLANS.. |
| SUBMIT A REVISED SCOPE OF WORK DOCUMENT FROM FLORIDA |
| STRUCTURES THAT CLEARLY REFLECTS THE EXISTING |
| CONDITIONS AND THE ENTIRE SCOPE OF WORK TO BE DONE TO |
| THE TOILET ROOMS. WPB AMEND. TO FBC SEC. 107.2.1. 2ND |
| REQUEST. |
| 2) THE SCOPE OF WORK FROM ALL FLORIDA STRUCTURES DATED |
| 1/19/17 NOTES THAT ALL PLUMBING IS EXISTING AND ONLY |
| REPLACING SUPPLY LINES & STOPS YET YOU HAVE LISTED |
| REPLACEMENT OF KITCHEN SINK, VANITIES, WATER HEATER, |
| TOILETS, ETC.CLARIFY.AGAIN, SHOW THE SCOPE OF THE |
| PLUMBING WORK ON THE PLANS. WPB AMEND. TO FBC 107.2.1. |
| 3) ARE THESE TOILET ROOMS EXISTING HANDICAPPED |
| ACCESSIBLE TOILET ROOMS OR ARE THEY BEING MADE INTO |
| HANDICAPPED ACCESSIBLE TOILET ROOMS. INDICATE THIS ON |
| THE PLANS.WPB AMEND. TO FBC SEC.107.2.1. |
| 4) THE SCOPE OF WORK DATED 1/19/17 REFERS TO REPLACING |
| SHOWER TRIM AND NEW GLASS DOOR YET THERE IS NO SHOWER |
| SHOWN ON THE PLANS. THE PLANS ARE VAGUE AND DO NOT |
| REFLECT THE SCOPE OF WORK OR EXISTING |
| CONDITIONS.CLARIFY. |
| 5) IF THESE ARE CURRENTLY BOTH HANDICAPPED ACCESSIBLE |
| TOILET ROOMS THEY HAVE TO REMAIN HANDICAPPED ACCESSIBLE |
| TOILET ROOMS. YOU CANNOT REDUCE THE LEVEL OF |
| ACCESSIBILITY BY ONLY HAVING ONE ACCESSIBLE TOILET |
| ROOM. CLARIFY. |
| 6) GRAB BARS SHALL COMPLY WITH FBC ACCESSIBILITY |
| SEC.604.5,609. 2ND REQUEST. |
| 7) ACCESSIBLE LAVATORIES IN HANDICAPPED ACCESSIBLE |
| TOILET ROOMS SHALL COMPLY WITH FBC-ACCESS. SEC.606, |
| 606.2, 606.3, 606.4,606.5..SHOW COMPLIANCE ON THE |
| PLANS. |
| 8) SHOW THE REQUIRED CLEAR FLOOR SPACES REQUIRED FOR |
| THE HANDICAPPED ACCESSIBLE FIXTURES PER |
| FBC-ACCESSIBILITY SECS. 604.3,606. |
| 9) VOID ALL OLD DOCUMENTS IN THE SUBMITTAL PACKAGE.WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 10) IS THE WASHER ATTACHING TO EXISTING LINES/OUTLETS |
| OR TO NEW SANITARY/ WATER LINES? IF NEW, SUBMIT A |
| SANITARY AND WATER RISER FOR REVIEW. IF CONNECTING TO |
| EXISTING, NOTE SUCH ON THE PLANS. |
| 11) THE HEIGHT OF THE KITCHEN COUNTER SHALL COMPLY WITH |
| THE FBC-ACCESS. SECS.606.2,606.3, 606.4,606.5. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |