2017-01-27 09:11:141)THE WORK DESCRIPTION DOCUMENT INDICATES THAT THESE
 ARE ADA TOILET ROOMS.THE REVISED PLANS DO NOT CLEARLY
 REFLECT THE SCOPE OF WORK AS OUTLINED IN THE WORK
 DESCRIPTION DOCUMENT. SHOW THE LOCATION OF THE EXISTING
 PLUMBING FIXTURES IN RESTROOMS #1 & #2 AND THE FIXTURE
 CLEARANCES FOR THE FIXTURES TO ENSURE CONTINUED
 COMPLIANCE WITH THE FL. ACCESSIBILITY CODE.
 2) SHOW THE LOCATION OF THE GRAB BARS ON THE PLAN.
 INSTALLATION OF GRAB BARS SHALL COMPLY WITH THE
 FBC-ACCESSIBILITY SECS. 604.5, 609.
 3) LAVATORIES SHALL COMPLY WITH FBC-ACCESSIBILITY
 SEC.606.
 4) INDICATE THE CAPACITY (GALS.) OF THE WATER HEATER ON
 THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  