Plan Review Notes
Plan Review Notes For Permit 17010976
Permit Number 17010976
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-17 15:26:05PLAN REVIEW FAILED
  
 1) NEED FAULT CURRENT CALCULATION FOR THE SERVICE PER
 110.24 (A,B)
 2) MAIN CIRCUIT BREAKER IS RATED AT 130 AMPERES? NOT A
 STANDARD SIZE 240.6
 3) CIRCUIT 11,15,17,19, AS SHOWN SHALL BE GFCI
 PROTECTED 210.8
 4) CIRCUIT #18 SHOWS 3 - 3WAY SWITCHES, NEEDS TO BE 2 -
 3WAYS AND A 4 WAY
 5) PANEL IN STORAGE ROOM NEEDS AT LEAST 36" OF FRONTAL
 CLEARANCE 110.26
 6) NO EXIT OR EMERGENCY LIGHTS SHOWN ON DRAWINGS
  