Plan Review Notes
Plan Review Notes For Permit 17010975
Permit Number 17010975
Review Stop G
Sequence Number 1
Notes
Date Text
2017-01-27 05:41:111) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER TO THE MOST REMOTE OUTLET IN THE BUILDING AND /
 OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1. I
 CANNOT REVIEW FOR COMPLIANCE WITHOUT THIS DISTANCE.
 2) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) HAVE
 BEEN USED IN THE DESIGN OF THE GAS SYSTEM. REFER TO THE
 2014 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES
 402.4 (1) THRU 402.4 (37) .
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  