Plan Review Notes For Permit 17010975 |
Permit Number |
17010975 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-01-27 05:41:11 | 1) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | METER TO THE MOST REMOTE OUTLET IN THE BUILDING AND / | | OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1. I | | CANNOT REVIEW FOR COMPLIANCE WITHOUT THIS DISTANCE. | | 2) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) HAVE | | BEEN USED IN THE DESIGN OF THE GAS SYSTEM. REFER TO THE | | 2014 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES | | 402.4 (1) THRU 402.4 (37) . | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | | | | | |
|