2017-01-30 07:52:18 | SEE COMMENTS FROM PRELINARY REVIEW 17010803: |
| |
| |
| |
| 1) BUILDING PROVISO: THE SECOND LIMITING FACTOR HAS TO |
| DO WITH THE IMPORTANCE FACTOR OF THE BUILDING AS PART |
| OF THE WIND DESIGN CRITERIA. PAGE 5 OF 8 WIND SPEED |
| RATING INDICATES THE RATING IS TAKEN AT 90 MPH VASD |
| CATEGORY B AND BUILDING RISK CATEGORY II. |
| |
| THE RISK CATEGORY IS FIGURED LOW. SEE THE 2014 FBC-B |
| TABLE 1604.5 RISK CATEGORY III STRUCTURES INCLUDES |
| ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF 300 OR |
| MORE. THE IMPORTANCE FACTOR FOR A RISK CATEGORY II |
| STRUCTURE IS 1.0 WHEREAS THE IMPORTANCE FACTOR FOR A |
| RISK CATEGORY III STRUCTURE IS A 1.15. THE LIMITING |
| FACTOR APPEARS TO BE THE PURLINS IN A EXPOSURE C @ 59 |
| MPH (VASD). WITH THE IMPORTANCE FACTOR OF 1.15 IN AN |
| EXPOSURE C THE PURLIN LIMITATION WOULD BE APPROXIMATELY |
| 51.30 MPH VASD. |
| |
| THE EVENT MAY NOT PROCEED IF THE WIND SPEED IS FORECAST |
| TO EXCEED 50 MPH (VASD) AND THE FABRIC SHALL BE REMOVED |
| FROM THE STRUCTURE BEFORE 50 MPH (VASD) WIND SPEED IS |
| EXPERIENCED. STATE ON PLANS. |
| |
| |