Plan Review Notes
Plan Review Notes For Permit 17010899
Permit Number 17010899
Review Stop E
Sequence Number 1
Notes
Date Text
2017-02-15 08:21:59INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN. FBC
 107.3.5
 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 3. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 4. PLEASE ADDRESS WALL SPACE RECEPTACLE REQUIREMENTS
 PER FBC RES E3901.2.2, 1. ANY SPACE THAT IS 2FT OR MORE
 IN WIDTH. SEE BEDROOM WALLS ADJACENT TO NEW CLOSET.
 5. SHOW A RECEPTACLE W/P GFCI PROTECTED AT THE HVAC AC
 LOCATION FOR SERVICE PER FBC RES E3901.12 HVAC OUTLET
 6. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 7. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR
 LAUNDRY ROOM 1500VA. FBC RES E3703.2 AND 4
 8. ARC FAULT REQUIMENTS SHALL APPLY TO ALL AREAS AS
 NOTED ON FBC RES E3902.12
 9. UPDATE ALL CODE REFERENCES TO NEC 2011 NOT 2005. SEE
 ABOVE CODES IN EFFECT.
 10. PROVIDE A NOTE TO COMPLY WITH TAMPER RESISTANT
 RECEPTACLES PER FBC RES 4002.14
 11. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  