2017-12-22 12:33:04 | 3RD REVIEW FBC-2014 RESIDENTIAL. |
| PERMIT #17010898 |
| 8/17/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| SOME OF THE 1ST REVIEW COMMENTS STILL EXIST. I HAVE |
| REPRINTED THEM BELOW WITH ADDITIONAL COMMENTS AND |
| CLARIFICATIONS. |
| |
| 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS |
| WITH CORRESPONDING DRAWINGS AND DETAILS ON THE PLAN. |
| |
| NEW COMMENT: THE REVISED PLAN IS INDICATING A REPLACED |
| AIR HANDLER. PLEASE PROVIDE ON THE PLAN AN AC EQUIPMENT |
| SCHEDULE THAT INCLUDES THE AIR HANDLER AND THE |
| CONDENSER, AND SUBMIT AN AHRI CERTIFICATE FOR THE |
| SYSTEM- SECTION R101.4.7 FBC-14 ENERGY CONSERVATION. |
| |
| NEW COMMENT: THE LOCATION OF THE AIR HANDLER APPEARS TO |
| HAVE CHANGED. PLEASE SHOW ALL ALTERATIONS TO THE |
| EXISTING SUPPLY AND RETURN SYSTEM, AND INDICATE THE |
| REQUIRED CLEARANCES FOR THE AIR HANDLER IN THE CLOSET |
| AS REQUIRED BY SECTION M1305.1.1. |
| |
| NEW COMMENT: THE LOCATION OF THE CONDENSER APPEARS TO |
| HAVE CHANGED. PLEASE PROVIDE STRUCTURAL DETAILS FOR |
| INSTALLATION OF THE PAD AND MOUNTING OF THE CONDENSER |
| TO THE PAD- SECTION M1305.1.4.1 & M1307.2 FBC-14 |
| RESIDENTIAL. |
| |
| 2) SUBMIT DOCUMENTATION OF ENERGY CONSERVATION |
| COMPLIANCE AS REQUIRED BY SECTIONS R101.4.3, R101.5.1 |
| FBC-14 ENERGY CONSERVATION CODE. |
| |
| 3) SUBMIT TWO COPIES OF WPB BUILDING DEPARTMENT AC |
| CHANGE OUT FORM. |
| |