2017-02-09 07:43:441ST REVIEW FBC-2014 RESIDENTIAL.
 PERMIT #17010898
 2/9/17
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 WITH CORRESPONDING DRAWINGS AND DETAILS ON THE PLAN.
 CLARIFY IF THE EXISTING AC SYSTEM WILL BE REPLACED OR
 ALTERED AS PART OF THE RENOVATION.
  
 2) INDICATE HOW THE BATHROOMS WILL BE VENTILATED USING
 EITHER OPERABLE OPENINGS TO THE OUTDOORS PER SECTION
 R303.3, OR MECHANICALLY PER M1507.4.
  
 3) PROVIDE EXHAUST VENTILATION FOR THE KITCHEN- SEE
 SECTIONS M1503- M1507 FOR COMPLIANCE METHODS.
  
 4) THE PLAN INDICATES A FIREPLACE THAT APPEARS TO BE A
 NEW INSTALLATION. PLEASE PROVIDE AN EQUIPMENT SCHEDULE
 ON THE PLAN THAT LISTS THE MAKE AND MODEL OF THE UNIT,
 AND TYPE- GAS-FIRED, WOOD BURNING, ELECTRIC ETC. A)
 SUBMIT MANUIFACTURER'S SPECIFICATIONS FOR THE UNIT AND
 THE VENT SYSTEM. B) PROVIDE A VENTING DIAGRAM THAT
 INDICATES THE TYPE AND SIZE OF VENT MATERIAL, LENGTH OF
 VENT
  
 RUN AND LOCATION OF VENT TERMIANTION CAP.
  
 5) SUBMIT DOCUMENTATION OF ENERGY CONSERVATION
 COMPLIANCE AS REQUIRED BY SECTIONS R101.4.3, R101.5.1
 FBC-14 ENERGY CONSERVATION CODE.
  