Plan Review Notes For Permit 17010898 |
Permit Number |
17010898 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-02 14:41:47 | 1ST REVIEW | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] CORRECT ELECTRICAL NOTE TO THE CURRENT APPPLICABLE | | CODE NEC 2011 ( FBC-R 2014 ) | | | | 2] AFCI PROTECTION ISN'T LIMITED TO THE BEDROOMS BUT IN | | ACCORDANCE NEC 210.12(B) ( FBC-R E3902.13 ) SEE | | PROVISIONS. | | | | 3] PROVIDE A GFCI SERVICE RECEPTACLE OUTLET WITHIN 25' | | OF THE C/U. NEC 210.63 ( FBC-R E3901.11 ) | | | | 4] ADD A NOTE THAT 75% OF LUMINAIRES SHALL BE HIGH | | EFFICIENT PER FBC-E R404.1. | | | | 5] THE MAIN DISCONNECT SHALL BE FUSIBLE FOR | | OVER-CURRENT PROTECTION PER NEC 230.90 ( FBC-R E3606.3 | | ). | | | | 6] WASHER ( LAUNDRY) CIRCUIT SHALL BE INCLUDED IN LOAD | | CALCS IN ACCORDANCE WITH NEC 220.52(B) ( FBC-R E3704.2 | | ). | | | | 7] SHOW DRYER BREAKER & WIRE SIZE ON PANEL SCHEDULE. | | FBC 107 | | | | |
|