Plan Review Notes
Plan Review Notes For Permit 17010898
Permit Number 17010898
Review Stop E
Sequence Number 1
Notes
Date Text
2017-02-02 14:41:471ST REVIEW
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] CORRECT ELECTRICAL NOTE TO THE CURRENT APPPLICABLE
 CODE NEC 2011 ( FBC-R 2014 )
  
 2] AFCI PROTECTION ISN'T LIMITED TO THE BEDROOMS BUT IN
 ACCORDANCE NEC 210.12(B) ( FBC-R E3902.13 ) SEE
 PROVISIONS.
  
 3] PROVIDE A GFCI SERVICE RECEPTACLE OUTLET WITHIN 25'
 OF THE C/U. NEC 210.63 ( FBC-R E3901.11 )
  
 4] ADD A NOTE THAT 75% OF LUMINAIRES SHALL BE HIGH
 EFFICIENT PER FBC-E R404.1.
  
 5] THE MAIN DISCONNECT SHALL BE FUSIBLE FOR
 OVER-CURRENT PROTECTION PER NEC 230.90 ( FBC-R E3606.3
 ).
  
 6] WASHER ( LAUNDRY) CIRCUIT SHALL BE INCLUDED IN LOAD
 CALCS IN ACCORDANCE WITH NEC 220.52(B) ( FBC-R E3704.2
 ).
  
 7] SHOW DRYER BREAKER & WIRE SIZE ON PANEL SCHEDULE.
 FBC 107
  
  