2017-04-10 13:43:411) THE LETTER THAT WAS SUBMITTED FROM GLIDDEN SPINA
 PARTNERS FOR THE OCCUPANT LOAD FOR THE REQUIRED
 SANITARY FACILITIES IS UNACCEPTABLE. THE NON-ASSEMBLY
 ROOM NUMBERS ARE LACKING THE CORRESPONDING SQUARE
 FOOTAGE OF EACH ROOM IN ORDER TO CONFIRM THE NEW
 OCCUPANT LOAD. WITHOUT THIS INFORMATION I CANNOT
 DETERMINE THE MINIMUM REQUIRED SANITARY FACILITIES AND
 THIS FACILITY SHALL COMPLY WITH THE POTTY PARITY
 REQUIREMENTS AS MANDATED IN THE 2014 FBC-PLUMBING
 SEC.403.1.3. I DISCUSSED THIS ITEM IN LENGTH WITH THE
 REPRESENTATIVE FROM GLIDDEN SPINA IN A MEETING AND I
 PROVIDED CLEAR DIRECTION AS TO WHAT WOULD BE REQUIRED
 TO MEET THE EXCEPTION LISTED IN SEC. 603.1.3. THE
 DIRECTION THAT I PROVIDED WAS NOT FOLLOWED AND
 THEREFORE THE EXCEPTION HAS NOT BEEN MET. 2ND REQUEST.
 2) SHT. P5.1 - THE VENT FOR THE TRENCH DRAIN LOCATED IN
 ROOM #111 DOES NOT COMPLY WITH 2014 FBC-PLUMBING
 SEC.905.3. THE VENT SHALL CONNECT TO THE HORIZONTAL
 DRAIN ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 3) THE POTABLE WATER CONNECTION TO THE BOILER SHALL BE
 EQUIPPED WITH A BACKFLOW PREVENTER WITH AN INTERMEDIATE
 VENT COMPLYING WITH ASSA 1012 OR CSA B64.3 PER FBC
 -PLUMBING SEC. 608.16.2. THE NOTE ON THE PLAN REFERS TO
 MANUFACTURER REQUIREMENTS. THIS IS A PLUMBING CODE
 REQUIREMENT AND THE PROPER BACKFLOW DEVICE SHALL BE
 PROVIDED. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW